Service settings manual
Heating curve steepness tells us, what temperature is required for the heating bodies by
a determined outdoor temperature. The steepness setting depends on the type of heating
system (floor, wall, radiator, convector heating) and insulation of the building.
HEAT CURVE
If you have enough data, you can determine the heating curve steepness with a calcula-
tion, otherwise from experience, based from the evaluation of heating system dimension-
ing and building insulation.
The steepness is set correct, if the room temperature remains stable, even by large out-
door temperature changes.
Until the outdoor temperature remains above + 5 °C, you can adjust the room tempera-
ture with changing day or night temperature or with parallel shift of the heating curve.
If it gets colder in the building, while the outdoor temperature is dropping, then the heat
curve steepness is set too low
-
you should increase the setting.
If the object by low outdoor temperatures gets warmer, the heat curve steepness needs
to be decreased.
The maximum steepness increase/decrease should not be greater than 0,1 to 0,2 units at
one observation. At least 24 hours must expire between two observations.
Adjusting the heating curve steepness
Parameter
Function
Parameter description
Setting range Default
value
P2.2
PARALLEL SHIFT OF
HEATING CURVE
Parallel shift of heating curve (calculated stand pipe
temperature).
Use this setting to eliminate deviation between actual and
set-point room temperature.
-15 ÷ 15 K
0
P2.3
DURATION OF BOOST
HEATING
Duration of boosted room temperature by changeover
from night to day heating period.
0 ÷ 200 min
0
P2.4 ROOM
TEMPERATURE
INCREASE BY BOOST
HEATING
Setting of boost temperature by changeover from night to
day heating period.
0 ÷ 8 K
4
P2.5
PRIORITY OF D. H. W.
WARMING
Setting if d. h. w. warming has priority to room heating. 0- NO
1- YES
0
Settings for heat source
:
Parameter
Function
Parameter description
Setting range Default
value
P3.1
MINIMUM BOILER
TEMPERATURE
Setting of minimal boiler temperature.
10 ÷ 90 °C
40
Settings for heating circuit
: