Requirement of installation
■
Please observe the following requirement.Otherwise, it may cause the product
aging and breakdown.
The applicable ambient temperature
of this product is in the range of
-10
℃~
40
℃
.
Locations where freezing could happen.
It’s prohibited to install in the uneven
surface.(Flatness shall be 3mm below.)
Otherwise, it may damage the
product or cause fire.
40℃
Distortion results in reducing the
separation performance.
Do not install the product where it is
exposed to oil fumes.
Do not install the product in the place
with many dust.
Impeller deformation may be caused
by sand and dust piling up, which may
affect the performance.
■
The lowest surface of this product
should be installed above 2.3m from
the floor after installation.
■
The distance between product and
ceiling must be 50mm above.
The ceiling is excessively close
to air inlet that may reduce the
separation performance.
■
Please install the product horizontally,
don’t vertically install the product.
It could affect the performance
of bearing.
■
Ensure the space among products is
20
~
40mm when multiple products
operate in row.
■
Please block the clearance between
wall and product.
Prevent product
from sucking in
outdoor air from
clearances.
50mm above
20
~
40mm
2.3m above
Easy for installation.
Avoiding any accident.