Address Words Description
Unit
Format
0x0002
2
Voltage
V
float
0x0004
2
Current
A
float
0x0006
2
Network frequency
Hz
float
0x0008
2
Current CosPhi
float
0x000a
2
Active power
W
float
0x000c
2
Fundamental reactive power
var
float
0x000e
2
No compensation power
var
float
0x0010
2
Apparent power
VA
float
0x0012
2
THD
%
float
0x0014
2
Temperature
°C
float
0x0016
2
Overtemperature switch-off
float
0x0018
2
Voltage 3
rd
harmonic
%
float
0x001a
2
Voltage 5
th
harmonic
%
float
0x001c
2
Voltage 7
rd
harmonic
%
float
0x001e
2
Voltage 9
rd
harmonic
%
float
0x0020
2
Voltage 11
rd
harmonic
%
float
0x0022
2
Voltage 13
rd
harmonic
%
float
0x0024
2
Maximum missing compensation power var
float
0x0026
2
Relay states (12 bit: bit 0 = stage 1 - bit
11 = stage 12 // bit 13 = error message)
bitwise
unsigned
long
0x0028
2
Messages (bit coded)
unsigned
long
0x002a
2
Error messages (bit coded)
unsigned
long
14.5 Data points
Data points can be read via the command 0x04 (read input registers) in accordance with
table 1.
Data point description for the Modbus protocol