background image

9

1. Timed current limit "TCL":  In this mode the drive will turn off after being in current limit

for a preset time.  The time period is adjustable with the TCL trimpot from 0.5-15

seconds and is factory set for approximately seven (7) seconds.  

TCL provides

electronic motor overload protection.

Application Note:

  After the control times out in TCL, it can be reset using the Start

Switch by setting the switch to the "STOP" position and then to "START," or by
disconnecting and reconnecting the AC line.  If the Start Switch is jumpered out, the
control can be restarted after timing out in TCL, by disconnecting and reconnecting the
AC line.  Note, the Overload lamp will remain lighted until the control is reset.

2. Non-Timed Current Limit "NTCL":  In this mode the drive will reach the preset current

limit during overload and stay at that level until a fuse blows or the drive is manually

turned off.  If non-timed CL operation is desired, move jumper J5 from the factory set

"TCL" position to the "NTCL" position.  The NTCL position must be used when

operating in the Torque Mode.  See section II, A on page 5.

F. J6 – Tach-generator voltage –

 (Note:  Selection of this jumper

position is not required if tach-generator feedback is not used.)  If

tach-generator feedback is used, select the J6 position (

7V

, 20/30V,

50V) which corresponds to the tach-generator voltage in 

Volts/1000

RPM

.  The selection of J6 position is based on a maximum motor

speed of 1800 RPM.  If other than standard tach-generator voltages

and motor speeds are used, an external resistor (RT) may be used

(1/2 watt rating).
1. Install resistor (RT) in series with either tach-generator lead.

2. Place J6 in "7V" position.

3. Calculate the value of (RT) as follows: 

RT = [(1.64 x VT x S) - 20,000] ohms

VT = Tach Voltage in Volts/1000 RPM

{

S = Base speed of motor in RPM

Note:  For tach-generator feedback, Jumper J3 must be in the "T" position.

G. J7 – Signal Input Voltage –

 The output of this control is normally controlled with the main

potentiometer.  However, an 

Isolated

 analog voltage may also be used in place of a

potentiometer.  The control can be scaled for either a 0-5VDC  or 0-

10VDC by placing J7 in the appropriate position "5V" or 

"10V"

.  The

scaling can be further adjusted with the "Max" trimpot.  See section IV,

F 2, on page 12 for wiring information.

Note:  If an 

Isolated

 input signal is not available an accessory Signal Isolator Model KBSI-

240D (KB P/N-9431) can be installed.  The KBSI-240D accepts a wide range of signal voltage

and current.  An Installation Kit containing Auto/Man Switch and required wiring is also

available (P/N 9377).

III. MOUNTING

Mount the control in a vertical position on a flat surface.  Be sure to leave enough room below

the bottom of the control to allow for the AC line and motor connections.  Although the control

is designed for outdoor and washdown use, care should be taken to avoid extremely

hazardous locations where physical damage can occur.  

Note:  Do not use this control in

an explosion proof application.

  If the control is mounted in a closed, unventilated cabinet,

remember to allow for proper heat dissipation.  If full rating is required, a minimum enclosure

size of 12" W x 24" H x 12" D should be used.

Front Cover - The KBPC case is designed with a hinge so that when the front cover is open,

all wiring stays intact.  To open the cover, the four cover screws must be loosened, so they

no longer are engaged in the case bottom.  Note that these screws are captive and the front

cover holes are threaded.  After mounting and wiring, close the front cover, making sure all

wires are contained within the enclosure and the gasket is in place around the cover lip.

Tighten all four cover screws so that the gasket is slightly compressed.  

Do not overtighten.

50V

20/30V

7V

J6

10V

Summary of Contents for KBPC-240D

Page 1: ...has been added which can be used to turn equipment on or off as a function of drive status Off Stop Run The General Performance Specifications Electrical Ratings Mechanical Specifications and Connecti...

Page 2: ...AND OPERATING INSTRUCTIONS MODEL KBPC 240D KB Part No 9338 Black Case Part No 9342 White Case NEMA 4X IP 65 SCR Speed and Torque Control Designed For DC Motors Rated 1 50 1 HP 90VDC 1 25 2 HP 180VDC...

Page 3: ...e Input and Motor Voltage with J2 and J3 Jumper Position 10 9 Field Connections Shunt Wound Motors Only 11 10 Armature Fuse Chart 13 11 Parts List 17 18 FIGURES 1 Control Layout 3 2 Mechanical Specifi...

Page 4: ...and F2 Connect half voltage field wires 90 volt motors with 50 volt fields and 180 volt motors with 100 volt fields to F1 and L1 See sec IV C on page 11 2 SPEED OR TORQUE MODE Jumper J1 is factory set...

Page 5: ...laration of Conformity Installation of a CE approved RFI filter KBRF 200A KB P N 9945A or equivalent is required Additional shielded motor cable and or AC line cables may be required along with a sign...

Page 6: ...3 FIG 1 CONTROL LAYOUT Illustrates Factory Setting of Jumpers and Approximate Trimpot Settings...

Page 7: ...4 INCHES mm FIG 2 MECHANICAL SPECIFICATIONS TM TM...

Page 8: ...Line VDC IR Comp Range at 230VAC Line VDC CL Range Range Setting Timed CL Range Sec Voltage Following Linearity Base Speed 115 or 230 50 60 1 0 90 0 180 0 90 100 50 200 100 1 50 1 015 75 1 25 2 03 1 5...

Page 9: ...motor load exceeds the torque setting the motor will stall the Overload LED will light and the drive will apply a constant preset torque based on the potentiometer setting The Overload LED will light...

Page 10: ...D TORQUE MODE B J2A J2B Input AC Line Voltage Select proper input line voltage 115VAC or 230VAC by placing both J2A and J2B in the correct corresponding positions 115V or 230V C J3 Armature Voltage Ou...

Page 11: ...ting Application Note Subfractional Horsepower Motors For subfractional motors with current ratings below 2 5 amps the KBPC can be modified as follows Note Before making this modification you must hav...

Page 12: ...Base speed of motor in RPM Note For tach generator feedback Jumper J3 must be in the T position G J7 Signal Input Voltage The output of this control is normally controlled with the main potentiometer...

Page 13: ...AC Line and Armature connection To maintain the watertight integrity of the control be sure to use suitable watertight connectors and wiring which are appropriate for the application Two 875 22 2 mm k...

Page 14: ...ains powered without motor rotating for an extended period of time TABLE 9 FIELD CONNECTIONS Shunt Wound Motors Only AC Line Voltage VAC Motor Voltage Field Voltage VDC Field Connection 115 90 100 F F...

Page 15: ...be installed Model KBSI 240D P N 9431 see figure 17 p 20 for signal isolator wiring diagrams Connect the isolated input voltage to terminal P2 and P1 See fig 12 Note Be sure jumper J7 corresponds to...

Page 16: ...ture fuse is not supplied and must be installed for control to operate VI OPERATION WARNING Read Safety Warning on page 2 before attempting to operate the control or severe injury or death can result...

Page 17: ...oximately seven 7 seconds and full rotation is approximately fifteen 15 seconds D Deceleration DECEL The DECEL trimpot sets the amount of time it takes the control to go from full speed to minimum spe...

Page 18: ...the AC line is connected to the control B Stop Indicator STOP This lamp will glow YELLOW when the control is placed in the STOP mode with the Start Stop Switch C Overload Indicator CL When the motor i...

Page 19: ...hased seperately E ON OFF AC Line Switch P N 9341 This option is desirable if a positive AC Line disconnect is required The switch can be installed in lieu of the Start Stop Switch which can be easily...

Page 20: ...20 FIG 17 CONNECTION DIAGRAMS FOR KBPC 240D WITH KBSI 240D SIGNAL ISOLATOR...

Page 21: ...21 APRM PC Electronic FWD BRK REV FIG 18 INTERNAL CONNECTION DIAGRAM FIG 19 CONNECTION DIAGRAMS FOR AVAILABLE OPTIONS...

Page 22: ...ee expressed or implied and we are not responsible for any expense including installation and removal inconvenience or consequential damage including injury to any person caused by items of our manufa...

Page 23: ...ety Warning on Page 1 The information contained in this manual is intended to be accurate However the Manufacturer retains the right to make changes in design which may not be included herein TM A COM...

Page 24: ...nection 5 2B 230V Connection 5 3 Current Input Signal Connection 6 4 Voltage Input Signal Connections 7 5A Leader Multiple Follower Voltage Following System Single Main Motor 9 5B Leader Multiple Foll...

Page 25: ...be worn and insulat ed adjustment tools must be used when working with drive under power This product is con structed of materials plastics metals carbon silicon etc which may be a potential hazard Pr...

Page 26: ...rom a voltage to current input A built in power supply enables the KBSI 240D to be controlled with a 5K remote poten tiometer connect potentiometer to terminals P1 5 and 6 see page 9 The potentiome te...

Page 27: ...IFICATIONS INCHES mm Illustrates Factory Setting of Jumpers and Approximate Trimpot Settings 3 1 MAX P1 VOLT CUR J1 MIN 2 3 4 5 6 7 8 9 10 4 mounting holes for 6 screws 2 244 57 0 0 276 7 00 0 276 7 0...

Page 28: ...er Requirements 115 or 208 230V AC 50 60 Hz 1 Signal Input Voltage 2 0 25 0 120 0 550V DC Signal Input Current 2 1 5 4 20 10 50mA 3 Maximum Output Voltage 10 Volts Maximum Output Current 10mA Range of...

Page 29: ...Input Terminals A voltage or current signal from a microprocessor tachometer transducer etc is to be con nected to terminals 5 through 8 The selection of the proper terminal is based on the maximum le...

Page 30: ...ll Resistor with Color Code Brown Black Red Install the 1k 1 4W resistor across Terminals 5 and 6 Set Jumper J1 in VOLT position Procedure to Calibrate the Signal Isolator When Using Current Signal In...

Page 31: ...igure 4 1 Connect a 10V DC meter digital meter is suggested to terminals 9 and 10 2 Apply the maximum input voltage that would be supplied from tach transducer etc 3 Adjust the MAX trimpot to the desi...

Page 32: ...imum voltage 3 Trimpots allow approximately 20 turns for the full range of adjustment If during the adjust ment procedure the output stops changing try reversing the direction of rotation of trimpot I...

Page 33: ...1 4 QD Connect as above WARNING If Signal Isolator is connected to multiple speed controls 1 Multiple controls must be powered from the same phase of AC line 2 The positive input terminal to each spee...

Page 34: ...Manual mode which will allow man ual override of an automatic process See figure 6B FIGURE 6B PROCESS CONTROL WITH AUTO MANUAL SWITCH 9 10 KBSI 240D 5 7 90V DC Main Motor A A DC Speed Control Speed C...

Page 35: ...P2 KB CONTROL KBSI 240D The following circuit provides for dual pur pose usage of the speed pot In the AUTO mode it is used for ratio control and in the MAN mode it is used for manual speed adjust me...

Page 36: ...NOTES 12...

Page 37: ...NOTES 13...

Page 38: ...implied KB Electronics Inc is not responsible for any expense including instal lation and removal inconvenience or consequential damage including injury to any person caused by items of our manufactur...

Page 39: ...4 20 MA SIGNAL INPUT The 4 20 ma signal for remote speed control is connected to terminals 5 negative and 6 positive This terminal strip is on the back of the front cover to the Penta Drive controller...

Reviews: