installation manual
24
SW 5 Difinition
SW6 Difinition
SW7 Difinition
●
To prevent collapsing of deforming, please bend the pipe at its
biggest radius.
●
Use bender to get a small radius pipes.
Use the market brass pipe.
Be sure to use the same insulating materials when you buy the
brass pipe. (More than 9mm thick)
For 200T1 unit, a mainboard in the electric control should set
the code ENC1 to B; the other one should set the code ENC1
to 8;
For 250T1 unit, a mainboard in the electric control should set
the code ENC1 to C; the other one should set the code ENC1
to 9;
For 280T1 unit, a mainboard in the electric control should set
the code ENC1 to D; the other one should set the code ENC1
to 9;
When using central controller to control the indoor unit,
please pay attention to the address setting, as the 220T1,
250T1 and 280T1 units have two or more mainboards. We
suggest setting the neighbor address for the mainboards
in the same indoor unit. When using a central controller for
controlling, mainboards in the same unit must be opened
and closed at the same time, for avoiding the unexpected
incident.
For both T1
J1, J2 Definition
J1
l
without jumper "J1" fo r
auto restart function
J1
l
with jumper "J1" for
non-auto restart function
J2
l
r eserve d
0/1 Definition
ON
l
means 0
ON
l
means 1
Please adjust the code ENC1 to the suitable position (both
system A and B should be adjusted for 200T1, 250T1 and
280T1 indoor unit).
● Then expose the pipe (cover it with tapes after bending).
13.
TROUBLE SHOOTING
Table.13-1
NO.
Error code
Indication
1
Timer LED and run LED
flash together, or show
"FE"
No address when first time
power on
2
Defrost LED flash
or show "E0"
Mode conflict
3
Timer LED flash
or show "E1"
Communication error between
indoor and outdoor unit
4
Run LED flash
or show "E2"
Temp.sensor (T1) error
5
Run LED flash
or show "E3"
Temp.sensor (T2) error
6
Run LED flash
or show "E4"
Temp.sensor (T2B) error
7
Timer LED flash slowly
or show "E6"
DC FAN error
8
Defrost LED flash slowly
or show "E7"
EEPROM error
9
Alarm LED flash slowly
or show "Ed"
Outdoor unit error
10
Alarm LED flash
or show "EE"
Water level alarm
SW5
ON
1 2
l
00 means temp.compensation
value is 6
℃
under heat mode
SW5
ON
1 2
l
01 means temp.compensation
value is 2
℃
under heat mode
SW5
ON
1 2
l
10 means temp.compensation
value is 4
℃
under heat mode
SW5
ON
1 2
l
11 means temp.compensation
value is 8
℃
under heat mode
SW6
ON
1 2 3
l
1 means old display panel
l
0 means new display panel
SW6
ON
1 2 3
l
1 means auto air blow under
auto m ode
l
0 means auto air blow under
non-auto mode
SW6
ON
1 2 3
l
reserved
SW7
ON
1 2
l
standard
configuration
SW7
ON
1 2
l
last unit of