Kaysun KFC-CI-2T-300D Installation & Owner'S Manual Download Page 9

Installation & Owner’s Manual

8

6.2   Drainage test

7.1   Connect the cable

7.    WIRING

Check whether the drainpipe is unhindered

New built house should have this test done before paving 

the ceiling. 

1. Remove the test cover, and stow water of about 

2000ml to the water receiver through the stow tube. 

2. Turn on the power, and operate the air conditioner 

under the "COOLING" mode. Listen to the sound of the 

drain pump. Check whether the water is discharged well 

(a lag of 1min is allowed before discharging, according 

to the length of the drain pipe), and check whether water 

leaksfrom the joints.

CAUTIONS: If there is any malfunction, please resolve it 

immediately.

3. Stop the air conditioner for there minutes, check if 

everything is ok. If the drain hose is located unreasonable, 

water overflow will cause the Alarm indicator lamp flashing 

(For both cooling and heating type or cooling only type), 

even the water leak out from the water receiver.

4. Check the drain pump whether drain water immediately 

when alarm sound for the high water lever. If the water 

lever can't come down below to the limited water lever, the 

air conditioner will stop. Restart it until  turn off the power 

and drain off all the water.

Dissemble the bolts from the cover.(If there isn't a cover 

on  the outdoor unit, disassemble the bolts from the 

maintenance board, and pull it in the direction of the arrow 

to remove the protection board.)

Connect the connective cables to the terminals as 

identified with their respective mached numbers on the 

terminal block of indoor and outdoor units.

Re-install the cover or the protection board.

Gradient: higher 

than 1/100

four-way cassette:

slim four-way cassette:

<200mm

<200mm

0.8-1.0m

0.8-1.0m

Lean over 1/100

Lean over 1/100

Pump-pipe clasp  

(the fittings)

Pump-pipe clasp  

(the fittings)

Max. 1000mm

Max. 600mm

 Fig.6-1

 Fig.6-2

0.8~1.0 m

>1.0 m

a  

5. Turn off the power, drain the water away.

The drain plug is used to empty the water-receiver for 

maintenance of the air conditioner. Please stuff it imposition at 

all times during operation to avoid leakage.

The air conditioner should use separate power supply with 

rated voltage.

The external power supply to the air conditioner should 

have ground wiring, which is linked to the ground wiring of 

the indoor and outdoor unit.

The wiring work should be done by qualified persons 

according to circuit drawing.

An all-pole disconnection device which has at least 3mm 

separation distance in all pole and a residual current device 

(RCD) with the rating of above 10mA shall be incorporated in 

the fixed wiring according to the national rule.

The appliance shall be installed in accordance with national 

wiring regulations.

Be sure to locate the power wiring and the signal wring 

well to avoid cross-disturbance.

Do not turn on the power until you have checked carefully 

after wiring.  

Remark per EMC Directive 2004/108/EC

For to prevent flicker impressions during the start of the  

compressor (technical process), following installation 

conditions do apply.

1.   The power connection for the air conditioner has to be 

done at the main power distribution. The distribution 

has to be of alow impedance, normally the required 

impedance reaches at a 32 A fusing point.

2.   No other equipment has to be connected with this power 

line.

3.   For detailed installation acceptance please refer to your 

power supplier, if restrictions do apply for products like 

washing machines, air conditioners or electrical ovens. 

4.   For power details of the air conditioner refer to the rating 

plate of the product. 

5.   For any question contact your local dealer.

CAUTION

NOTE

Summary of Contents for KFC-CI-2T-300D

Page 1: ...y much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference KFC CI 2T 300D KFC CI 2T 500D KFC CI 4T 300D KFC CI 4T 500D KFC CI 2T 300D1 KFC CI 2T 500D1 KFC CI 4T 300D1 KFC CI 4T 500D1 ...

Page 2: ...e the set to fall water leakage electrical shock and fire The appliance must be installed 2 3m above floor The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the appliance shall be marked by word or by symbols with the direction of the flui...

Page 3: ... install the air conditioner in the following locations There is petrolatum existing There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hot spring The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existing There are inflammable materials or ...

Page 4: ...e hook 4 4 2 Installation hook 4 4 3 Installation paper board 1 1 4 Bolt M6 4 Tubing Fittings 5 Soundproof insulation sheath 2 2 Drainpipe Fittings 6 Out let pipe pipe 1 1 7 Out let pipe sheath 1 8 Out let pipe clasp 1 1 9 Tightening band 20 20 Remote controller Its Frame 10 Remote controller 1 1 11 Frame 1 1 12 Mounting screw ST2 9 10 C H 2 2 13 Alkaline dry batteries AM4 2 2 Others 14 Installati...

Page 5: ...3 Install the main body Face the concave side of the installation hooks toward the expansible hooks Determine the length of the installation hooks from the height of ceiling then cut off the unnecessary part If the ceiling is extremely high please determine the length of the installation hook according to facts If the drainpipe is awry leakage will be caused by the malfunction of the water level s...

Page 6: ...nner insulation Insulation local Central hole Grid switch All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail Bolt M6X12 Installation paper board Body Insulation local Side plate Insulation local Ceiling 10 12mm Body 10mm Slit Side plate Fig 5 1 Fig 5 3 Fig 5 5 Fig 5 8 ...

Page 7: ... pipe joint Connecting point of drain pipe Ground Ground Panel Panel Outlet Outlet 600mm ceiling hole 600mm ceiling hole Outlet Outlet Inlet Inlet Unit mm Tubing side FIGURES 3 Fig 5 12 Fig 5 13 Fig 5 16 Fig 5 17 Fig 5 14 Fig 5 15 Fig 5 18 Before suspending installation please connect the three way valve and its connected pipe to the main unit There are not three way valve and the connected pipe b...

Page 8: ...gthen drainpipe apply protective tube to wrap its indoor parts for ensuring the lengthen part connected tightly 7 In case the drainpipe outlet is higher than pumping connective pipe of the main body the drainpipe must be arranged upwards vertically by using connective assembly of the water outlet for vertical bending and the height of the drainpipe shall set to the defrosting pan surface no more t...

Page 9: ...8 1 0m Lean over 1 100 Lean over 1 100 Pump pipe clasp the fittings Pump pipe clasp the fittings Max 1000mm Max 600mm Fig 6 1 Fig 6 2 0 8 1 0 m 1 0 m a b 5 Turn off the power drain the water away The drain plug is used to empty the water receiver for maintenance of the air conditioner Please stuff it imposition at all times during operation to avoid leakage The air conditioner should use separate ...

Page 10: ...ether the switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow louver moves normally d Whether the room temperature is adjusted well e Whether the indicator lights normally f Whether the temporary buttons works well g Whether the drainage is normal h Whether there is vibration or abnormal noise during operation I Whether the ai...

Page 11: ...d mild detergent to clean it and dry out in cool place Caution Do not dry out the air filter under direct sunshine or with fire The air in side should face up when using vacuum cleaner See fig 9 3 The air in side should face down when using water See fig 9 4 Check and remove everything that might be blocking inlet and outlet vents of indoor units Clean air filters and casings of indoor units Refer...

Page 12: ...ries of remote controller exhausted or other problem of controller Wait for the comeback of power Switch on the power Replace the fuse Replace the batteries or check the controller Air flowing normally but completely can t cooling Temperature is not setted correctly Set the temperature properly Units start or stop frequently Air or no concreting gas in the watering circuit three way valve is malfu...

Page 13: ...icated on the display is FAN ONLY The temperature cannot be set during FAN mode The indication on the display disappears after a lapse of time Check whether the timer operation has come to an end when the TIMER OFF is indicated on the display The air conditioner operation will stop up to the set time The TIMER ON indicator goes off after a lapse of certain time Check whether the timer operation is...

Page 14: ...unning lamp timer lamp defrosting lamp alarm lamp 1 Room temperature sensor checking channel is abnor mal X X X 2 Evaporator sensor checking channel is abnormal X X X 3 EEPROM malfunction X X 4 Water level switch malfunction X X X 5 Indoor unit switch at long range controller is dialed to OFF X X X ...

Page 15: ...2020001A9002 V1 0 MDV08IU 026DW ...

Page 16: ......

Reviews: