Installation & Owner’s Manual

4

5.    FAN COIL UNIT INSTALLATION

5.1   Installation place

(refer to fig.5-1, fig.5-2, fig.5-3 and table 5-1 for specification.)

The indoor unit should be installed in a location that meets 

the following reauirements:

There is enough room for installation and maintenance.
The ceiling is horiztal, and its structure can endure the 

weight of the indoor unit.
The outlet and the inlet are not impeded, and the influence 

of external air is the least.
The air flow can reach throughout the room.
The connecting water pipe and drainpipe could be  

extracted out easily.
There is no direct radiation from heaters.

Keep indoor unit, outdoor unit, power supply wiring and  

transmission wiring at least 1 meter away from televisions  

and radios. This is to prevent image interference and  

noise in those electrical appliances. (Noise may be  

generated depending on the conditions under which the  

electric wave is generated, even if 1 meter is kept.) 

Cut off the knockout hole on the side plate with a nipper.

Cut the inner insulation of the hole portion with a cutter. 

(refer to fig.5-4)

Put the insulation tightly around the hole of the unit as   

shown.

The ends of the side plate and the inner insulation must be 

completely adhered without leaving any clearance along the  

circumference of the hole.

Make sure the inner surface of insulation tightly contacts the  

inner insulation edge and the side plate. 

 (refer to fig.5-5)

The center of the hole should be at the same position of  

that of the air conditioner body.
Determine the lengths and outlets of the connecting pipe,  

drainpipe and cables.
To balance the ceiling and to avoid vibration, please 

enforce the ceiling when necessary.

Drill four holes of Φ12mm, 50~55mm deep at the selected   

positions on the ceiling. Then embed the expansible hooks 

(fittings).

1  Cut a quadrangular hole of 880x880mm or 600x600mm in  

the ceiling according to the shape of the installation paper 

board. 

2  Select the position of installation hooks according to the  

hook holes on the installation board.

Preparing the connection hole 

Placing the insulation

The existing ceiling (to be horizontal)

CAUTION

5.2   Installation procedures for fresh air  

        intake duct connection

5.3   Install the main body

Face the concave side of the installation hooks toward 

the expansible hooks. Determine the length of the 

installation hooks from the height of ceiling, then cut off 

the unnecessary part.
If the ceiling is extremely high, please determine the length 

of the installation hook according to facts.

If the drainpipe is awry, leakage will be caused by the  

malfunction of the water-level switch.
Adjust the position to ensure the gaps between the body 

and the four sides of ceiling are even. The body's lower 

part should sink into the ceiling for 10~12 mm. 

(refer to 

fig.5-6)

In general, L is half of the screw length of the installation 

hook.

(refer to fig.5-6)

Locate the air conditioner firmly by wrenching the nuts  

after having adjusted the body's position well. 

(refer to 

fig.5-7)

Please first guarantee the flatness and horizontal of 

ceiling when installing it.
Refer to 1 mentioned above for others.

After installing the body, the four bolts(M6x12)must be 

fastened to the air conditioner onto ensure the body is 

grounded well.

Use the system in the following temperature for safe and 

effective operation.

Table 5-1

3  Adjust the hexangular nuts on the four installation hooks 

evenly, to ensure the balance of the body.

1  In the case of new built house, the hook can be embedded 

in advance (refer to 2 mentioned above). But it should be 

strong enough to bear the indoor unit and will not become 

loose because of concrete shrinking.

2  After installing the body, please fasten the installation 

paper  board onto the air conditioner with bolts(M6X12) to 

determine in advance the sizes and positions of the hole 

opening on ceiling.

(refer to fig.5-8)

1  If air conditioner is used outside the above conditions, it may 

cause the unit to function abnormally.

2  The phenomenon is normal that the surface of air 

conditioning may condense water when the relative larger 

humidity in room, please close the door and window.

3  Optimum performance will be achieved within these 

operating temperature range.

4  Water system operating pressuer: Max: 1.6MPa, Min: 

0.15MPa. 

3  Refer to 3 above for  installation.
4  Remove the installation paper board.

New built houses and ceilings

CAUTION

5.4   OPERATION RANGE

Temperature 

Mode

Outdoor 

temperature

Room  

temperature

water inlet 

temperature

Cooling operation

0°C~43°C

17°C~32°C

3°C~20°C

NOTE

Heating operating 

(cooling only type 

without)

-15°C~24°C

0°C~30°C

30°C~75°C

Summary of Contents for KFC-CI-2T-300D

Page 1: ...y much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference KFC CI 2T 300D KFC CI 2T 500D KFC CI 4T 300D KFC CI 4T 500D KFC CI 2T 300D1 KFC CI 2T 500D1 KFC CI 4T 300D1 KFC CI 4T 500D1 ...

Page 2: ...e the set to fall water leakage electrical shock and fire The appliance must be installed 2 3m above floor The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the appliance shall be marked by word or by symbols with the direction of the flui...

Page 3: ... install the air conditioner in the following locations There is petrolatum existing There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hot spring The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existing There are inflammable materials or ...

Page 4: ...e hook 4 4 2 Installation hook 4 4 3 Installation paper board 1 1 4 Bolt M6 4 Tubing Fittings 5 Soundproof insulation sheath 2 2 Drainpipe Fittings 6 Out let pipe pipe 1 1 7 Out let pipe sheath 1 8 Out let pipe clasp 1 1 9 Tightening band 20 20 Remote controller Its Frame 10 Remote controller 1 1 11 Frame 1 1 12 Mounting screw ST2 9 10 C H 2 2 13 Alkaline dry batteries AM4 2 2 Others 14 Installati...

Page 5: ...3 Install the main body Face the concave side of the installation hooks toward the expansible hooks Determine the length of the installation hooks from the height of ceiling then cut off the unnecessary part If the ceiling is extremely high please determine the length of the installation hook according to facts If the drainpipe is awry leakage will be caused by the malfunction of the water level s...

Page 6: ...nner insulation Insulation local Central hole Grid switch All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail Bolt M6X12 Installation paper board Body Insulation local Side plate Insulation local Ceiling 10 12mm Body 10mm Slit Side plate Fig 5 1 Fig 5 3 Fig 5 5 Fig 5 8 ...

Page 7: ... pipe joint Connecting point of drain pipe Ground Ground Panel Panel Outlet Outlet 600mm ceiling hole 600mm ceiling hole Outlet Outlet Inlet Inlet Unit mm Tubing side FIGURES 3 Fig 5 12 Fig 5 13 Fig 5 16 Fig 5 17 Fig 5 14 Fig 5 15 Fig 5 18 Before suspending installation please connect the three way valve and its connected pipe to the main unit There are not three way valve and the connected pipe b...

Page 8: ...gthen drainpipe apply protective tube to wrap its indoor parts for ensuring the lengthen part connected tightly 7 In case the drainpipe outlet is higher than pumping connective pipe of the main body the drainpipe must be arranged upwards vertically by using connective assembly of the water outlet for vertical bending and the height of the drainpipe shall set to the defrosting pan surface no more t...

Page 9: ...8 1 0m Lean over 1 100 Lean over 1 100 Pump pipe clasp the fittings Pump pipe clasp the fittings Max 1000mm Max 600mm Fig 6 1 Fig 6 2 0 8 1 0 m 1 0 m a b 5 Turn off the power drain the water away The drain plug is used to empty the water receiver for maintenance of the air conditioner Please stuff it imposition at all times during operation to avoid leakage The air conditioner should use separate ...

Page 10: ...ether the switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow louver moves normally d Whether the room temperature is adjusted well e Whether the indicator lights normally f Whether the temporary buttons works well g Whether the drainage is normal h Whether there is vibration or abnormal noise during operation I Whether the ai...

Page 11: ...d mild detergent to clean it and dry out in cool place Caution Do not dry out the air filter under direct sunshine or with fire The air in side should face up when using vacuum cleaner See fig 9 3 The air in side should face down when using water See fig 9 4 Check and remove everything that might be blocking inlet and outlet vents of indoor units Clean air filters and casings of indoor units Refer...

Page 12: ...ries of remote controller exhausted or other problem of controller Wait for the comeback of power Switch on the power Replace the fuse Replace the batteries or check the controller Air flowing normally but completely can t cooling Temperature is not setted correctly Set the temperature properly Units start or stop frequently Air or no concreting gas in the watering circuit three way valve is malfu...

Page 13: ...icated on the display is FAN ONLY The temperature cannot be set during FAN mode The indication on the display disappears after a lapse of time Check whether the timer operation has come to an end when the TIMER OFF is indicated on the display The air conditioner operation will stop up to the set time The TIMER ON indicator goes off after a lapse of certain time Check whether the timer operation is...

Page 14: ...unning lamp timer lamp defrosting lamp alarm lamp 1 Room temperature sensor checking channel is abnor mal X X X 2 Evaporator sensor checking channel is abnormal X X X 3 EEPROM malfunction X X 4 Water level switch malfunction X X X 5 Indoor unit switch at long range controller is dialed to OFF X X X ...

Page 15: ...2020001A9002 V1 0 MDV08IU 026DW ...

Page 16: ......

Reviews: