background image

12

Maintenance after a long period of non-use

Check for and remove anything that might be blocking the 

inlet and outlet vents of the indoor units and outdoor units.

Clean the unit casing and clean the filter. Refer to [Cleaning 

the filter] and "Cleaning the filter" for instructions. Re-install 

the filter before running the unit.

Turn on the power at least 12 hours before you want to use 

the unit to ensure it works properly. As soon as the power is 

turned on, the remote control display appears.

The following symptoms may be experienced during the 

normal operation of the unit and are not considered faults. 

Note: If you are not sure whether a fault has occurred, contact 

your supplier or service engineer immediately.

Symptom: When the ON/OFF button on the remote controller 

is  pressed, the unit does not immediately start running.

Cause: To protect certain system components, system start-

up or re-start is intentionally delayed for up to 12 minutes 

under some operating conditions. If the OPERATION LED on 

the unit's panel is lighting, the system is working normally and 

the unit will start after the intentional delay is complete.

Heating mode is running when the following panel lights are 

on:  operation and the "DEF./FAN LED indicator (cooling and 

heating type) or the fan only indicator (cooling only type)". 

When it starts but the compressor does not, the indoor 

unit activates protective measures because of the outlet 

temperature.

White mist is generated and emitted when the unit starts 

to operate in a very humid environment. This phenomenon 

will stop once the humidity in the room is reduced to normal 

levels.

The unit occasionally emits white mist when it runs in 

heating mode. This occurs when the system finishes periodic 

defrosting. Moisture that may accumulate on the unit's heat 

exchanger coil during defrosting becomes mist and is emitted 

from the unit.

6.  SYMPTOMS THAT ARE NOT FAULTS

Symptom 1: The unit will not run

Symptom 2: The unit emits white mist 

A continuous sound (other than that made by the unit's fan) is  

heard when the unit is running in cooling mode. This is caused 

by the unit's drain pump (on units that have a drain pump).

A squeaking sound is heard when the unit stops after running 

in heating mode. This is caused by plastic components cooling  

down and contracting.

A slight hissing sound is heard when the unit is running. This 

is the sound of refrigerant flowing through the unit and through 

the piping that connects the unit to the rest of the system. This 

sound is more noticeable when the unit starts/stops running 

and the flow of refrigerant begins/ceases.

This can occur when the unit first runs after a long idle period.

If smells such as those of strong-smelling food or tobacco 

smoke are present in the room, they can enter the unit, leave 

trace deposits on the unit's internal components, and later be 

emitted from the unit.

Sections 7.2 and 7.3 describe some initial troubleshooting 

steps that can be taken when an error occurs. If these steps do 

not resolve the issue, arrange for a professional technician to 

investigate the problem. Do not attempt further investigations 

or troubleshooting yourself.

If any of the following errors occur, power the unit off, contact 

a professional technician immediately and do not attempt 

troubleshooting yourself:

- A safety device such as a fuse or circuit breaker frequently 

blows/trips.

- An object or water enters the unit.

- Water is leaking from the unit.

Symptom 3: The unit emits sounds

Symptom 4: Dust is emitted from the unit 

Symptom 5: The unit gives off a strange odor

7. TROUBLESHOOTING

7.1 General

Summary of Contents for KCOF-22 DN4.0

Page 1: ...Thank you for purchasing this air conditioning unit Read this manual carefully before using the unit and retain it for future reference OWNER S MANUAL VRF DC Indoor Units...

Page 2: ...0 KPDF 45 DN4 0 KPDF 56 DN4 0 KPDF 71 DN4 0 KPDF 80 DN4 0 KPDF 90 DN4 0 KPDF 112 DN4 0 KPDF 140 DN4 0 KPDHF 71 DN4 0 KPDHF 90 DN4 0 KPDHF 112 DN4 0 KPDHF 140 DN4 0 KPDHF 160 DN4 0 KPDHF 200 DN4 0 KPD...

Page 3: ...s staples and other metal packaging components can be sharp and should be disposed of carefully to avoid injury Do not attempt to inspect or repair this unit yourself This unit should only be serviced...

Page 4: ...exposure to corrosive or harmful gases such as acidic or alkaline gases may occur To avoid excessive noise or vibration the unit should be installed in a position that can bear the unit s weight and...

Page 5: ...tu adjustment to three direction or two direction please contact the local dealer Grounding Screw in the control box Horizontal Air Outlet Louver Air Intake Air Filter inside Horizontal Air Outlet Lou...

Page 6: ...ke Air Outlet Louver F4 front air intake Version I Vertical unit with casing Front air intake and top air outlet It can be installed on the floor or hung on the wall Drain pipe Heat Exchanger Electric...

Page 7: ...ch the unit runs stably are given in Table 3 1 Temperature Mode Indoor temperature Cooling mode 17 C 32 C If the indoor humidity is above 80 condensation may form on the surface of the unit Heating mo...

Page 8: ...aintain a proper air distribution Close doors and windows Avoid direct exposure to outlet air as it may be too cool or hot This applies especially to children the elderly and people with disabilities...

Page 9: ...ust the air direction up and down CAUTION Water may drip from the unit if the direction of outlet air is adjusted downward during cooling operation The uneven distribution of indoor temperature will b...

Page 10: ...mode cooling mode heating mode Situation When the room is cool or after running the air conditioner for one hour At the start of the operation or at other times when the room is not fully cooled At ti...

Page 11: ...the finish Do not use benzene thinner polishing powder or similar solvents for cleaning These may cause the plastic surface to crack or warp The control box cables originally connected to the electri...

Page 12: ...te Type For Console Type Air filter Special function filter Fig 5 8 The filter is housed in the lower part of the unit in Version II and III to take in air from below or from rear To remove the filter...

Page 13: ...t grille by reversing steps 1 and 2 and connect the control box cables to the corresponding terminals in the main body 2 Dismantle the air filter 3 Clean the air filter Fig 5 14 Fig 5 15 Fig 5 16 Do n...

Page 14: ...s occurs when the system finishes periodic defrosting Moisture that may accumulate on the unit s heat exchanger coil during defrosting becomes mist and is emitted from the unit 6 SYMPTOMSTHATARENOTFAU...

Page 15: ...to check the following Too much or too little refrigerant No gas in the refrigerant circuit The outdoor unit compressors have malfunctioned The power supply voltage is too high or too low There is a...

Page 16: ...speed can be selected during COOL FAN ONLY and HEAT The remote controller signal is not transmitted even when the ON OFF button is pushed A power cut has occurred the power to the premises has been cu...

Page 17: ...aged main PCB 3 Indoor ambient temperature sensor error OPERATION LED flashes rapidly E2 Temperature sensor not connected properly or has malfunctioned Damaged main PCB 4 Indoor heat exchanger mid poi...

Page 18: ...16126000003108 V1 0...

Page 19: ......

Page 20: ......

Reviews: