CAUTION:
The operator should not reset any other parameters.
To set these parameters please follow the programming guide for each parameter. The programming
guide shows the menus and key entries required to modify each parameter. The programming guides
for each parameter and an example are included at the end of this section.
Please note that it is recommended that any field-modified parameters be recorded on the “BDA
CONTROLLER SETTINGS - As-Built” sheet provided with the BDA. This As-built document should be
available for reference should the controller require replacement.
7.6 BDA Controller Field Settings Parameters
AS-Built
Reference
BDA Parameter
Descriptions
1A Uplink
Gain
Set the overall Uplink gain of the BDA.
Refer to FIELD SETTINGS – MAIN MENU PROGRAMMING GUIDE
1B Downlink
Gain Set the overall Downlink gain of the BDA.
Refer to FIELD SETTINGS – MAIN MENU PROGRAMMING GUIDE
1C Uplink
AGC
Set AGC based on number of channel for Uplink. The AGC setting is
from 0 to 255.
Refer to Table 2.1 for desired AGC level and FIELD SETTINGS – MAIN
MENU PROGRAMMING GUIDE to set AGC parameter value
1D Downlink
AGC Set AGC based on number of channel for Downlink. The AGC setting is
from 0 to 255.
Refer to Table 2.1 for desired AGC level and FIELD SETTINGS – MAIN
MENU PROGRAMMING GUIDE to set AGC parameter value
1E
Backup Power
This parameter can be set to either SUPPLY or BATTERY.
Refer to FIELD SETTINGS – MAIN MENU PROGRAMMING GUIDE
1F Beep
Audio indicator –
not available on this model
2B Password
New password can be set through the Controller main menu. If BDA
password is lost, contact network manager.
Refer to CONTROLLER – MAIN MENU PROGRAMMING GUIDE
8A
Temp Shutdown
If set to “Yes”, BDA will shutdown once the BDA reaches the
Temperature limit setting (not recommended in the Public safety
applications).
Refer to TEMPERATURE – MAIN MENU PROGRAMMING GUIDE
8B Temp
Limit
Alarm warning will issued once the BDA reach this Maximum operating
temperature setting.
Refer to TEMPERATURE – MAIN MENU PROGRAMMING GUIDE
8C Recovery
Temp After shutting itself down, BDA will turn back on when it reaches this
recovery temperature setting.
Refer to TEMPERATURE – MAIN MENU PROGRAMMING GUIDE
Summary of Contents for BDA1300
Page 29: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 33 of 51 ...
Page 30: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 34 of 51 ...
Page 31: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 35 of 51 ...
Page 32: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 36 of 51 ...
Page 33: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 37 of 51 ...
Page 34: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 38 of 51 ...
Page 35: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 39 of 51 ...
Page 36: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 40 of 51 ...
Page 37: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 41 of 51 ...
Page 38: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 42 of 51 ...
Page 39: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 43 of 51 ...
Page 40: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 44 of 51 ...
Page 41: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 45 of 51 ...
Page 42: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 46 of 51 ...
Page 43: ...BDA1300 Equipment Manual DCM000000018 Kaval Telecom Inc Page 47 of 51 ...