background image

12

www.katusensor.com

Display menu

Display menu

Level 1 menu

Level 2 menu

The one-circuit switch does

 not have this function

Summary of Contents for PS500 Series

Page 1: ...Operating instruction Electronic pressure sensor PS500 Series Sensor and controller Flow pressure temperature level position...

Page 2: ...nance conditions Security of loss Such as Incorrect use Incorrect installation Incorrect operation or operation in violation of the provisions of this operation manual No liability shall be assumed fo...

Page 3: ...mply may result in fatal injury danger An identifiable hazard Failure to comply may result in fatal injury and damage to equipment or plant parts warning It means a danger Failure to comply may result...

Page 4: ...n needs The device which can rotate at 330 guarantees the best viewing Angle in different mounting modes Switching function If the switch is higher or lower than the set switching limit SP rP its swit...

Page 5: ...ructions are intended to protect users from dangerous situations and or prevent material damage In the operating instructions the severity of the potential risk can be indicated by the following signa...

Page 6: ...rmally closed Window function FNO normally open FNC normally closed Hold down or for at least 1s After 1 second The setting value can be changed At the press of a button the value increases Hold the b...

Page 7: ...least 1s After 1 second The setting value can be changed At the press of a button the value increases Hold the button down and the value will keep changing dr1 OUT1 shutdown delay The factory default...

Page 8: ...2 3 brown black white blue SP1 NPN Analog quantity 12 30VDC 1 5 4 2 3 brown black blue white SP1 The pressure switch can only be debugged and operated by authorized personnel Note that the casing sur...

Page 9: ...alue increases Hold the button down and the value will keep changing rp2 Switch 2 Reset value Factory default value is SP2 0 5 Hold down or for at least 1s After 1 second The setting value can be chan...

Page 10: ...ill keep changing dr1 OUT1 shutdown delay The factory default is 0s Hold or for at least 1s After 1 second The setting value can be changed At the press of a button the value increases Hold the button...

Page 11: ...e setting value can be changed At the press of a button the value increases Hold the button down and the value will keep changing H0 Maximum system pressure in history Hold down or for at least 1s Aft...

Page 12: ...button down and the value will keep changing daa Display refresh time analog 0 1s factory default is 0 01 Hold down or for at least 1s After 1 second The setting value can be changed At the press of...

Page 13: ...12 www katusensor com Display menu Display menu Level 1 menu Level 2 menu The one circuit switch does not have this function...

Page 14: ...13 www katusensor com Display menu Level 2 menu No analog model does not have this function...

Page 15: ...ping process data flow IO Link communication and display Factory default 0 06 Hold down or for at least 1s After 1 second The setting value can be changed At the press of a button the value increases...

Page 16: ...Katu Electronic Kunshan Co Ltd The phone number is 400 150 8815 Website www katusensor com Factory No 1120 Jinyang East Road Kunshan City Suzhou City...

Reviews: