KATANA S610M Inverter Specialized for Elevator Manual
Function
Code
Parameter Name
Setting Range
Factory Default
Value
(UPS operation)
This function code is utilized to set max. given exciting current value of UPS operation when under IF
control. This value is based on the rated current of inverter, 800 represents 80.0% of the rated current of
inverter.
6.8
Input & Output Terminal Setting (Group F07)
Function Code
Parameter Name
Setting Range
Factory Default
Value
F07.00
Function selection of input terminal X1
0
~
50
0
F07.01
Function selection of input terminal X2
0
~
50
0
F07.02
Function selection of input terminal X3
0
~
50
0
F07.03
Function selection of input terminal X4
0
~
50
0
F07.04
Function selection of input terminal X5
0
~
50
0
F07.05
Function selection of input terminal X6
0
~
50
0
F07.06
Function selection of input terminal X7
0
~
50
0
F07.07
Function selection of input terminal X8
0
~
50
0
F07.08
Function selection of input terminal X9
(Reserved)
0
~
50
0
F07.09
Function selection of input terminal
X10
(Reserved)
0
~
50
0
Multifunctional input terminals, X1
~
X9, carry rich functions, which can be defined through setting
F07.00
~
F07.09 to satisfy various needs. Please refer to Table 6-1 for the parameter value and function:
Table 6-1 Multifunctional input functions list
Value
Corresponding function
Value
Corresponding function
0
Non Functional
1
Upward (UP-forward)
2
Downward (Reverse)
3
Multi-speed selection
1(MS1)
4
Multi-speed selection
2(MS2)
5
Multi-speed selection
3(MS3)
6
External reset input
7
External error input
8
Inspection input (INS)
9
Operation permission of
the inverter
10
Emergency operation
input
11
Operating contactor
feedback input (CSM)
12
Braking feedback input
(BSM)
13
Up forced deceleration
speed input (UPF)
14
Down forced
deceleration speed input
(DNF)
15
Upward leveling input
16
Downward leveling input 17~50
Reserved