The Central Supervisory Equipment shall employ supply line transient protection complying with the
Standard for Transient Voltage Surge Suppressors, UL 1449, with a maximum marked rating of 330
V.

The Central Supervisory Equipment shall employ signal line Transient protection complying with the
Standard for Protectors for Data Communications and Fire Alarm Circuits, UL 497B, with a maximum
marked rating of 50 V.

The Central Supervisory Equipment shall employ that communication circuits and network
components connected to the telecommunications network shall be protected by secondary
protectors for communication circuits. These protectors shall comply with the Standard for Secondary
Protectors for Communications Circuits, UL 497A. These protectors shall be used only in the
protected site of the telecommunications network.

UL 1076 

Compliance 

Notice (cont’d)

The Central Supervisory Equipment shall be installed in a temperature controlled environment. A
temperature controlled environment is defined as one that can be maintained between 13° - 35°C
(55° - 95°F) by HVAC system. Twenty-four hours on standby power shall be provided for the HVAC
system. The standby power system for the HVAC system may be supplied by an engine driven
generator alone. A standby battery is not required to be used.

A marking to identify the application and signaling function of the product is located on the inside of
the unit (inner door sticker).

For certified commercial proprietary control unit accessory applications, the requirements of UL
1076, Commercial Proprietary Control Unit Accessory also apply.

All alarms shall be reported and acknowledged in the following priority*:

1. Fire alarm and industrial supervision where a risk of injury to persons, or damage or destruction

of property may be involved

2. Hold-up or panic alarm
3. Burglar alarm
4. Watchman tour (Guard tour)
5. Fire-alarm supervision
6. Burglar-alarm supervision
7. Industrial supervision where a risk of injury to persons, or damage or destruction of property will

not be involved

* To set these priorities, please adjust the Event Parameters, found in EntraPass System.

The following Kantech readers were validated by UL for the UL 1076 standard: P225W26,
P225KPW26, P225XSF, P225KPXSF, P325W26, P325KPW26, P325XSF, P325KPXSF, and P600.

For remote alarm monitoring, the Kantech part number KT-3LED-PLATE must be installed. Refer to
the procedure 

Install the KT-3LED-PLATE 

on 

Page 17

 for details.

KT-NCC UL 

Compliance

In order to comply with UL listings, the following has to be met:

Use of a UL listed 60950 computer

Use of a UL recognized tamper switch on every housing cabinet for the KT-NCC

Use only UL listed or recognized cables

Use only UL listed or recognized adaptors

Use only a UL listed transformer such as Kantech TR1640P/UL

Use a Kantech KT-BATT-12, 12V/7Ah battery

The KT-CAB3000LDR and KT-CAB4000LDR have been evaluated by UL as alternate
enclosures

Note: 

The backup battery provides operation for up to 6 hours; This battery has only been tested for 
only 4 hours as per Section 33 of UL 294, fifth edition. A message will be sent to the monitoring 
station when the battery life has less than 4 hours remaining. 

Summary of Contents for KT-NCC

Page 1: ...DN1611 1809 KT NCC Network Communications Controller Installation Manual ...

Page 2: ...KT NCC to Controllers Loops 13 Connecting the Relays 14 Installing the KT 3LED PLATE 15 EntraPass Configuration 15 Installing Additional Sites 16 Installing the 12V 7Ah battery 16 Installing the AC Transformer 16 KT NCC Configuration 17 Pre Configuration 17 Configuration Scenarios 17 DHCP with Customer Server IP Address LAN 17 Static IP address 18 WAN Configuration 18 Port forwarding 19 Communicat...

Page 3: ...isconnect both poles simultaneously LINE and NEUTRAL 2 AVOID setting up the equipment near heaters air conditioners ventilators and or refrigerators DO NOT select a place that exposes your KT NCC to direct sunlight excessive heat moisture vapors chemicals or dust 3 If during the installation a knockout on the cabinet is removed it is the installer s responsibility to ensure that the same degree of...

Page 4: ...olombia Bogota Direct 57 1344 1422 Colombia Cali Direct 57 2891 2476 Colombia Medellin Direct 57 4204 0519 Costa Rica National Direct 506 4000 1655 Dominican Republic Santo Domingo Direct 1829 235 3047 El Salvador San Salvador Direct 503 2136 8703 Guatemala Guatemala City Direct 502 2268 1206 Mexico Mexico City Direct 5255 8526 1801 Panama Panama City Direct 507 836 6265 Peru Lima Direct 51 1642 9...

Page 5: ...00 0 4127 Belgium Direct 0800 76 452 Ireland Direct 1800 94 35 70 Nordic countries Direct 4544 94 90 01 Denmark Direct 4544 94 90 01 Greece Direct 00 800 3122 9453 Russia Direct 8 10 800 2052 1031 Turkey Direct 00 800 3192 3037 United Arab Emirates Direct 800 0310 7123 South Africa Direct 2721 100 3882 Country Region Phone Numbers Support Hours Email ...

Page 6: ...ial Proprietary Control Unit Accessory Section 83 2 with EntraPass and Redundant Server alarm system features KT 300 Door Access Controllers IoProx Proximity readers and Trex request to exit devices other sensor devices temperature water level etc may be used as long as they are also UL 1076 Listed The EntraPass and Redundant Server shall be running at all time and manned 24 hours a day 365 days a...

Page 7: ...rietary control unit accessory applications the requirements of UL 1076 Commercial Proprietary Control Unit Accessory also apply All alarms shall be reported and acknowledged in the following priority 1 Fire alarm and industrial supervision where a risk of injury to persons or damage or destruction of property may be involved 2 Hold up or panic alarm 3 Burglar alarm 4 Watchman tour Guard tour 5 Fi...

Page 8: ...rmation technology equipment radio disturbance characteristics EN60950 Information technology equipment safety EN61000 6 1 Electromagnetic Compatibility EMC Generic Standards Immunity for residential commercial and light industrial environments EN61000 6 2 Electromagnetic Compatibility EMC Generic Standards Immunity for industrial environments ...

Page 9: ...pass back alarm systems guard tours dual custody etc The KT NCC s main task is to acquire information from all input channels and relay the results back to all output channels through the controller loops The KT NCC communicates with the server through an Ethernet 10 100 Base T port and indicates its communication status through a heartbeat LED The KT NCC will report low battery and battery failur...

Page 10: ... Dimensions 375 9 mm 14 8 in x 304 8 mm 12 0 in x 125 7 mm 4 95 in Cabinet Weight UL 4 0 kg 8 8 lb Cabinet Weight CE 4 8 kg 10 6 lb KT NCC Board dimension with heat sink 22 90 cm 9 in x 13 98 cm 5 1 2 in x 5 20 cm 2 1 16 in Communication Ports RS 485 x 2 RS 232 Ethernet 10 100 base T Communication Speed Up to 19 200 Baud for serial communication Firmware Flash Memory 16 MB SDRAM Memory 64 MB Prote...

Page 11: ...eway 7 loops 2 x RS 485 1 x RS 232 4 x IP Maximum Controllers per Loop RS 485 COM1 32 RS 485 COM2 32 RS 232 32 IP 1 8 IP 2 8 IP 3 8 IP 4 8 Number of Cards 56 000 Readers Keypads per Gateway 128 X 2 256 Door Lock Outputs per Gateway 128 X 2 256 Maximum Number of Floors 64 floors Access Levels 250 Access Door Groups 100 Relay Groups 100 Controller Groups 100 Access Code Groups 100 Operating System W...

Page 12: ...clude screws and locknuts Item Description KT NCC Notes 1 2 KT NCC PCB KT NCC CAB Note 1 KT NCC ACC KT NCC PCB ACC Note 2 KT NCC EU Notes 1 2 KT NCC PCB 1 1 1 Cabinet 1 1 1 VC 485 adapter cable 1 1 Ground wire PCB to cabinet 1 1 Ground wire door to cabinet 1 1 Green ground wire 18 AWG 20 cm 8 in 1 Tamper switch 1 1 Battery cable 1 1 1 KT NCC ACC 1 1 KT NCC PCB ACC 1 Inner door sticker for North Am...

Page 13: ...Network cable s Tool Checklist The following tools will be required to install the KT NCC Small screwdriver included in the KT NCC ACC and KT NCC PCB ACC kits 0 65 cm 0 25 in nut driver Wire strippers Small needlenose pliers Reading Checklist We strongly suggest that you keep the following documents close at hand EntraPass Global Edition Reference Manual DN1316 KT NCC Quick Configuration Guide DN1...

Page 14: ...selected wall using four screws fed through the mounting holes Refer to Figure 25 on Page 42 for details on the KT NCC enclosure For KT NCC UL Cabinet only In order for the KT NCC to comply with UL294 section 32 1 5 the installation technician has the responsibility of installing an AC powered LED outside the KT NCC cabinet and connect it to relay 2 on the KT NCC The LED must be visible at all tim...

Page 15: ...e resistor to install on the RS 485 terminals on the last controller of a loop 1 The two RS 485 terminals labeled COM 1 and COM 2 can be found next to the relay terminals at the bottom of the left side of the KT NCC board Wire the loops according to Figure 4 on Page 15 below The orange wire connects into the terminal the blue wire connects into the terminal and the white wire connects to the AUX 1...

Page 16: ...T NCC to comply with UL 294 section 32 1 5 the installation technician has the responsibility of installing an AC powered LED outside the KT NCC cabinet and connect it to relay 2 on the KT NCC PCB The LED must be visible at all time Figure 6 Onboard Relays CON1 RS 232 RS232 TX RS232 RX COM2 TX COM2 RX COM1 TX COM1 RX RELAY1 RELAY2 RELAY3 RELAY4 RS 232 EXPANSION BUS WHITE BLUE WHITE ORANGE VC 485 C...

Page 17: ...he red LED is ON it corresponds to the arm function and when the red LED is OFF it corresponds to the disarm function The system cannot be armed or disarmed when the Ready to arm green LED is OFF The electrical plate with 22 AWG wires made of stainless steel is considered as a standard Note The 3 LED plate must be located near the reader s that is are designed to arm or disarm the alarm system It ...

Page 18: ... to 4 hours if the AC supply is removed An internal battery verification will cut the battery power if the battery voltage level falls below 9 5 volts Installing the AC Transformer 1 Install the 16 5 VAC 40 VA class 2 transformer KT NCC unit will not start on battery alone Note That step doesn t apply to the KT NCC EU Cabinet 2 Power up the KT NCC 3 Make sure the KT NCC is in factory default befor...

Page 19: ...of a server and one or several KT NCCs connected to the server through a hub or switch Whatever the case an IP address has to be assigned so that the KT NCCs and the EntraPass server can communicate When the EntraPass server is used a static or DHCP address can be assigned to establish the communication When the customer server is used the DHCP server assigns a dynamic IP address WAN is generally ...

Page 20: ...ign Static IP address using the KT NCC Web Configuration Page or the KT Finder and configure gateway parameters See instructions on page 29 e Check the connection status See instructions on page 37 WAN Configuration You will use this type of setup in an environment where remote sites are protected with routers and they communicate with each other through the Internet a Initialize the KT NCC in fac...

Page 21: ...one to the same IP address If you install more than one KT NCC with a router you should use different ports for every KT NCC NT NCC Forward address Port Connection type Protocol Host router Server IP address 18002 TFTP firmware update UDP Server IP address 18701 Device communications UDP Host router for redundant server Server IP address 18702 Device communications UDP Remote router Device IP addr...

Page 22: ...munication timing will be more appropriate It is important for the communication timing to be well configured in order to avoid communication breakdowns The following table contains the parameters that will be defined in EntraPass Global Edition Software Table 5 KT NCC Communication Timings Once again we suggest that you consult the Network Administrator in order to measure the complexity of the n...

Page 23: ... 1 Press the Reset button Hard Reset A hard reset will reset the KT NCC to it s default values but will keep the IP address intact 1 Use the needlenose pliers to remove jumper JP2 2 Press the Reset button 3 You must wait until the blue LED starts to flash again approximately 15 seconds before you put jumper JP2 back in place Factory Reset We strongly suggest that you call Kantech Technical Support...

Page 24: ... Ethernet 1 to the server When configuring the KT NCC with the Web Configuration Page you must use a crossover cable to connect the Ethernet 2 directly to the RJ 45 connector of the workstation Note 1 The KT NCC Web Configuration Page is only accessible by the Ethernet 2 at IP address 192 168 0 2 Note 2 The Ethernet 1 is accessible by the KT Finder using Ethernet 1 MAC address 00 50 F9 xx xx xx At...

Page 25: ...component The components list displays the new KT NCC still not activated identified with the blue dot 6 Select the KT NCC component with the blue dot The Activate button will become enabled Click Activate to register the KT NCC with the EntraPass Global server The blue dot next to the KT NCC turns green The Edit button becomes enabled so that you can configure the security options 7 Close the Sys...

Page 26: ...raPass Global Server continued Figure 11 EntraPass Message List Desktop The messages to lookout for are KT NCC Update of platform CE KT NCC Started KT NCC Update of platform CE KT NCC Completed KT NCC Update of platform CE KT NCC Completed successfully ...

Page 27: ...ed The KT NCC gateway will appear along with a number on the right hand side of the dialog You can rename the KT NCC gateway in the French and English fields 3 Click the General tab 4 Select the Number of controller loops in the text box under Loop Configuration The KT NCC can physically support 7 controller loops 5 In the KT NCC Time Zone configuration area you must select the appropriate Time zo...

Page 28: ...tion is checked by default 11 Select the Obtain an IP address automatically option 12 Port 18710 is automatically assigned to the KT NCC by default It is advisable not to modify it 13 By default the Enable broadcast assignation box is checked Leave it to default 14 Click the Save icon 15 To verify if the server is communicating with the KT NCC you can monitor the incoming messages in the Desktop M...

Page 29: ...he computer used to configure the KT NCC This IP address is assigned by default to Ethernet port 2 for the KT NCC Web Configuration Page The IP address of the computer must be within the same segment For example 192 168 0 x where x can be any number between 3 and 256 Important Make sure that your network cable is NOT connected to the Ethernet Port 1 1 Connect the crossover cable to the Ethernet Po...

Page 30: ...l return to the KT NCC Web Configuration tool main window Meanwhile the KT NCC will reset The blue Heartbeat LED of the KT NCC will blink quickly to signal that the KT NCC is in reset mode The blue Heartbeat LED of the KT NCC will remain lit for 15 seconds to signal that the KT NCC is in startup mode The blue Heartbeat LED of the KT NCC will blink 4 times to signal that the KT NCC has reset but it...

Page 31: ...DN1611 1809 31 KT NCC Installation Manual Configuring with a Static IP Address continued 3 Enter the information gathered in the Configuration Information Sheet 4 Click on OK ...

Page 32: ... gateway in the French and English fields 3 Click the General tab 4 Select the Number of controller loops in the text box under Loop Configuration The KT NCC can physically support 7 controller loops 5 In the KT NCC Time Zone configuration area you must select the appropriate Time zone setting Note It is advisable to check with the Network Administrator if the site where you are installing the KT ...

Page 33: ... Use the Following IP Address Enter the IP address of the KT NCC Enter the Subnet Mask address When necessary enter the Gateway Router that the Network Administrator provided you Port 18710 is automatically assigned by default It is advisable not to modify it The option Broadcast configuration is selected by default Leave this option as is 12 Click the Save icon and close the Gateway dialog 13 To ...

Page 34: ...parameters Configuring Server Parameters 1 From the Options toolbar click the Server Parameters tab Figure 19 Server Parameters Dialog WAN 2 Select the Gateway tab then KT NCC 3 The option Inbound Server Router should be already checked 4 Enter the Public IP Address of inbound router or the Domain Name This address is assigned by the public network provider to whom you are connected 5 Click OK to ...

Page 35: ...e text box marked Gateway and scroll down the selection of gateways until you reach the KT NCC gateway you have just saved The KT NCC gateway will appear along with a number on the right hand side of the dialog You can rename the KT NCC gateway in the French and English fields ...

Page 36: ...efault 11 Select the Obtain an IP Address Automatically option 12 Port 18710 is automatically assigned to KT NCC by default It is advisable not to modify it However if you have to configure several KT NCCs ensure that every KT NCC has a unique port number This is necessary when forwarding ports to an IP address 13 The option Broadcast configuration is selected by default 14 Select the Public IP ad...

Page 37: ... the KT NCC that you just configured Upgrading Firmware After installing a new version of EntraPass Global Edition software and starting the application the system will automatically verify that both software and hardware versions are similar If this is not the case the system will perform an update automatically An event will be displayed in the Desktop Message list to indicate the progress of th...

Page 38: ... apply pressure to or deform the batteries Ensure that the above precautions are strictly observed by related departments including but not limited to production sales and outside contractors Regarding the recommended backup battery 12 VDC 7 Ah It is the technician s responsibility to assure that the disposal of used batteries is made according to the waste recovery and recycling regulations appli...

Page 39: ...Printed Circuit Board ETHERNET 1 HEARTBEAT BLUE LED RS 485 COM 1 2 RELAYS 1 4 BATTERY CONNECTOR ETHERNET 2 ETHERNET LEDS JP2 JP3 RESET LITHIUM ION BATTERY AC POWER AUX POWER EARTH GROUND MAC ADDRESS LOCATION TAMPER SWITCH RS 232 COM3 ...

Page 40: ...D BE AC DC PWR PWR 6 CONDUCTOR COM1 COM3 TO ETHERNET NETWORK TO CONTROLLERS TO CONTROLLERS ETH 2 ETH 1 TXRX 100 BATT TO CONTROLLERS ORANGE BLUE WHITE COM2 RS 485 EXPANSION BUS EXPLODED VIEW OPTIONAL 120 VAC 16 5 VAC 40 VA Class 2 WIRE IN PLUG IN ALSO AVAILABLE NOTE DO NOT CONNECT TO RECEPTACLE CONTROLLED BY A SWITCH CABINET PEM LOCKNUT EARTH GROUND SEALED RECHARGEABLE BATTERY 12 VOLT 7AMP HR RECEI...

Page 41: ...DN1611 1809 41 Figure 24 KT NCC Wiring Diagram for Europe and Asia ...

Page 42: ... REX Z11 Z11 C Z12 Z12 DOOR DOOR C REX REX C Z16 Z16 INPUT DOOR 4 INPUT DOOR 4 READER DOOR 4 READER DOOR 4 Z15 Z15 C P N 566 472K P N 566 472K REV E REV E 485 485 COM1 COM1 12V 12V HEARTBEAT HEARTBEAT SPI ACTIVE SPI ACTIVE COM1 RX COM1 RX COM1 TX COM1 TX COM2 TX COM2 TX RS232 TX RS232 TX LOCK4 LOCK4 LOCK3 LOCK3 LOCK2 LOCK2 LOCK1 LOCK1 RELAY3 RELAY3 RELAY2 RELAY2 RELAY1 RELAY1 AC PWR AC PWR CPU JTA...

Page 43: ...ith the server Steady on 15 30 sec KT NCC is starting up Quick flashes May last from 15 30 sec Preparing to reboot DO NOT POWER DOWN OR RESET DURING THIS PROCESS Quick flashes May last up to 90 sec Firmware update DO NOT POWER DOWN OR RESET DURING THIS PROCESS 1 long flash sec KT NCC is in factory reset mode 4 flashes on per sec and 1 sec steady off KT NCC is in hard reset mode ...

Page 44: ...______ IP Address is ___Static ___DHCP Reserved address recommended RS 485 Loop 1 Name __________________________________________ RS 485 Loop 2 Name __________________________________________ RS 232 Loop 3 Name __________________________________________ IP Loop 4 Name ______________________________________________ IP Loop 5 Name ______________________________________________ IP Loop 6 Name _______...

Page 45: ...DN1611 1809 45 ...

Page 46: ... 2018 Tyco Security Products All Rights Reserved www kantech com DN1611 1809 ...

Reviews: