1. Operating Instructions
Carrying out measurements
Perform a self-test of the unit. Connect the two
test probes L1 and L2 together. The continuity
LED (6) will be lit, & an audible tone should be
heard.
Before any test, check the unit on a known
voltage source or approved voltage proving unit.
If the unit is defective it should be put out of service
& returned to KANE for repair.
7
2. AC Voltage Indication
8
V. Display & Controls
1. Test Probe (-) L1
2. Test Probe (+) L2
3. LED’s for voltage indication
4. LED for single - pole test
5. Right & Left LED, phase rotation indication
6. LED for continuity
7. LCD for voltage display (only DL6790)
8. Contact electrode for double-pole test of
phase rotation & single-pole test
9. Torch button on the back
10. Positive LED
11. Negative LED
12. Battery Compartment
AC Voltage
LED on
LED off
Always hold the test probes by the handles
behind the finger guards. Observe all the safety
notices at all times.
An audible tone is present when an AC voltage &
a negative DC voltage are indicated.
The maximum switch on time is 30 seconds.
When this time has elapsed, you must wait 10
minutes before retesting.
Connect probes to the voltage source observing
the polarity of the test probes, L2 is the positive
probe, L1 is the negative probe.
For AC voltage the value is indicated on the
LEDs (3) & on the LCD display.
The + & - LEDs are illuminated & buzzer is
audible.