background image

Warning! Warns of potential danger, & to 

comply with the instruction manual.

Caution! Dangerous voltage, potential risk 

of electrical shock.

Equipment protected throughout by 

double or reinforced insulation. Complies 

with IEC 536, class II

Suitable for live working

CE Symbol of conformity confirms conformity 

with relevant EU directives. The meter 

complies with EMC directives (2004/ 1 08/ 

EC), the Low Voltage Directive (described 

in the standard EN 61010·1, 61243·3.

The DL6780/90 meets the standard 

(2012/19/EU) WEEE. This marking 

indicates that this product should not be 

disposed with other household wastes 

throughout the EC. To prevent possible 

harm to the environment or human health 

from uncontrolled waste disposal, recycle 

it responsibly to promote the sustainable 

reuse of material resources. To return your 

used device, please use the return & 

collection systems or contact the retailer 

where the product was purchased. They 

can take this product for environmental safe 

recycling.

The instruction manual contains 

information & references, necessary for 

safe operation & maintenance of the 

instrument. Prior to using the instrument 

the user is kindly requested to thoroughly 

read the instruction manual & comply with 

it in all sections.

III. Instrument Symbols (continued)

IV. KANE-VCT Specification

5

6

CAT IV Applicable to test & measuring 

circuits connected at the source of 

the building’s low-voltage MAINS 

installation.

Failure to read the instruction manual or 

to follow the warnings and references 

contained herein can result in serious bodily 

injury or instrument damage. The respective 

accident prevention regulations established 

by the professional associations are to be 

strictly enforced at all times.

III. Instrument & Manual Symbols

Symbols displayed on the instrument & in the 

instruction manual:

EN

61010-1

CAT IV

600V

KANE-VCT Voltage Indicator Specification

2 Pole Voltage Indication

Voltage range

 

12 - 690V AC/DC

LED Resolution

12, 24, 50, 120, 230, 400 & 690V

LCD Resolution

1 V ±

Voltage detection

Automatic

Frequency range

0 - 400Hz

Peak current

3.5mA

Operation time

30 seconds

Acoustic AC/DC signal

Auto power on

>12V AC/DC

IP rating

IP65

Single Pole Indication

Voltage range

 

100 - 690V AC

Frequency range

50 - 400Hz

Continuity

Acoustic & visual

Measurement range

0 - 400kΩ

Phase Rotation Test

Voltage range

 

100 - 690V AC

Frequency

45 - 65Hz

Over Voltage Protection

690V AC/DC

Other Information

Dimensions

225mm x 70mm x 28mm

Weight (net)

210g

Power supply

2 x 1.5V (RO3) AAA (supplied)

EAN

5039046000533

Summary of Contents for KANE-VCT

Page 1: ...EN 61010 1 CAT IV 600V Instruction Manual KANE VCT Voltage Continuity Tester Voltage Indication 12 690V AC DC with Continuity Inventory No MAN00160 Rev 1 0221 February 2021...

Page 2: ...this instrument is assured when operated within the specifications in this instruction manual The product identified above conforms to the requirements of council directive 2014 35 EU Contents I Overv...

Page 3: ...ified nominal voltages The different indicating signals of the voltage indicator are not to be used for measuring purposes Before using a voltage indicator at locations with a high background noise le...

Page 4: ...requested to thoroughly read the instruction manual comply with it in all sections III Instrument Symbols continued IV KANE VCT Specification 5 6 CAT IV Applicable to test measuring circuits connecte...

Page 5: ...7 LCD for voltage display only DL6790 8 Contact electrode for double pole test of phase rotation single pole test 9 Torch button on the back 10 Positive LED 11 Negative LED 12 Battery Compartment AC...

Page 6: ...a function test prior to this test This unit can be used as a single pole voltage indicator when the batteries are inserted The single pole test is intended only as a quick check The circuit must be...

Page 7: ...s test This unit can determine the phase rotation within a three phase supply Connect test probe L2 to the supposed phase 2 the test probe L1 to the supposed phase 1 If the R LED illuminates the phase...

Page 8: ...KANE s discretion This warranty covers normal use does not cover damage which occurs in shipment or failure which results from alteration tampering accident misuse abuse neglect or improper maintenan...

Page 9: ...NE and the KANE logo registered in the UK and elsewhere are trademarks of Kane Group Limited used under licence All other marks are trademarks of their respective holders 2021 Kane International Limit...