Please  note  that  when  the  ambient  temperature  is  hot,  as  it  often  is  the  case  in  some 
commercial 

environment

,  the  temperature  of  the  controller  will  get  hotter.  This  is  because  the

heat  dissipation  is  mostly  determined  by  the  temperature  gradient  (the  temperature  difference 
between the ambient and the controller) instead of absolute temperature of the controller itself. If 
the controller reaches 50 °C when the ambient is at 20 °C, it will reach 70 °C when the ambient 
is at 40 °C.  

Solutions to reduce the heat stress on the controller

1) Use  hot  water.  If  you  fill  the  pot  with  hot  water  that  has  a  temperature  close  to  the  set
temperature, the heat dissipation of the controller is not an issue. As we have mentioned, once 
the temperature is close to the set point temperature, the controller starts to pulse (PWM) the 
power. The effective current is much lower, making heat not an issue. 

2) Limit  maximum  output  power.  If  you  set  output  reduction  parameter  to  80%,  then,  a  15A
heater

 

will  become  a  12A  heater.  It  will  take  25%  longer  time  to  heat  up  the  pot,  but  the 

controller will not over heat. 

In addition to these solutions, following information will also help you to manage the heat. Place 
the controller in the right place. The SSR of Auber WS series controller is mounted in the 
bottom of chassis. The chassis is made of 3 mm thick aluminum for good heat dissipation. Do not 
cover the controller with any insulation. If you are running at 15 A with a large pot, placing the 
controller in a well ventilated area and tilting the instrument up with its front legs will help it to 
remove  heat  more  efficiently.  However,  the  tilted  position  may  result  in  water  collected  at  the 
back frame. Although the controller is splash proof, you should avoid water to be dripped on the 
controller

.

Increase  the  P  value.  This  can  only  provide  limited  help  for  reducing  the  heat.  P  is  the 
proportional band. P=200 means the proportional band is 20.0 degrees. When the temperature 
is raised to less than 20 degree from the set point temperature, the controller will start to reduce 
the power sooner. But if the integration time is set to very short, the controller might start to run 
at full power again soon.  

Copyright 

2018

Kamweld Industries, Inc. 

 All Rights Reserved.

No part of this manual shall be copied, reproduced, or transmitted in any way without the prior, written consent of A

Kamweld 

Industries

Kamweld Industries 

 retains the exclusive rights to all information included in this document.

Summary of Contents for KAM-TC1000

Page 1: ...emperature and high wattage appliances and your safety is paramount SAFETY WARNINGS This controller is designed only to be used with limited power device and paring thermal cutoff protection such as a...

Page 2: ...ler off unplug the power cord and contact Kamweld Industries at 617 558 7500 before using it again Clean the controller only when it is cool and unplugged Specifications Input voltage 100 to 240 VAC 5...

Page 3: ...ff the heater power is off When it is flashing it means the heater is on and off intermittently to reduce the power output 3 SET Key For showing current temperature settings entering parameters settin...

Page 4: ...ing indicator A dot at the lower right corner When the dot flashing the value is editable pressing the or key to change the value The layout of the controller back panel is shown in Figure 2 Figure 2...

Page 5: ...the power switch to turn on the controller The LED display will show 8 8 8 8 for 2 seconds and then display the current temperature Then turn off the controller Plug the power cord from the device WEL...

Page 6: ...gram the time of the rest of the steps to zero To program the temperature profile press SET key once The display will show C 1 for one second and then display the temperature setting for step 1 Use an...

Page 7: ...T SET Figure 5 Temperature profile programming flow chart Here is the one step heating program The temperature profile is programmed to start at 150 F for 600 minutes of heating Table 1 Initial progra...

Page 8: ...when you first press key controller will show P 2 in the window If then you press Time key the controller will show P 40 with the Time Indicator lit At normal operating mode press the Time key item 6...

Page 9: ...perating the controller in Fahrenheit you need to divide the P by 1 8 when changing the temperature unit to Celsius ON OFF mode If P is set to 0 the control mode will be changed from PID mode to ON OF...

Page 10: ...ater 1 second for every 10 seconds This parameter should set at 2 second for heating with an electric heater When controlling a solenoid valve or a compressor of refrigerator the T should be set to 10...

Page 11: ...lue should be 2 for most application After change the PID parameter the controller needs to be turned off and on again for the best result 30 Lck 166 P 7 I 600 d 150 at 0 t 2 SET 3 sec SET SET SET SET...

Page 12: ...sate for the error produced by sensor Each unit is 1 degree e g if the temperature displays 2 C in ice water mixture set SC 2 will make the display to shown 0 degree OUT Output power reduction It is e...

Page 13: ...delay The Anti short is the delay time to turn on the cooler E g refrigerator If the cooler is compressor based compressor should not be turned on immediately when it is at high pressure just after t...

Page 14: ...le if AH set to 290 the buzzer will be on at 291 and off at 290 When the buzzer is on the display window will flashing between AH1 and the current temperature AL Low limit alarm for probe For example...

Page 15: ...a program has been entered the user can save this current program as a Program for future use Under the normal operating mode press and hold SET key for 3 seconds until the Parameter Window displays L...

Page 16: ...show 0 Use and keys to adjust the display to 1 and press SET The display will show rC for a second and then the value End If press SET key now you will exit this mode without overwriting any existing...

Page 17: ...l operating mode to recall a Program press and hold SET key for 3 seconds until the Parameter Window displays LOCK Release the SET The display will show 0 Use and keys to adjust the display to 3 and p...

Page 18: ...T briefly and enter the program below C 1 120 t 1 2 0 C 2 290 F 2 160 C 3 130 F 3 30 0 You can leave the rest of steps as their default values To store to Program b1 long press SET key set LoCK 2 choo...

Page 19: ...ent single step program is C 1 120 3 Set current C 1 to 200 then store current program back to recipe b1 Now the b1 recipe is C 1 200 4 Change PrG y current b1 recipe is C 1 200 F 1 2 0 C 2 190 F 2 16...

Page 20: ...erating mode press and hold SET key for 3 seconds until LED display LoCK and then release the SET key The display will show 0 then Use key to adjust the number to 50 and press SET key again to enter T...

Page 21: ...current will produce about 1 3 watts of heat When 12 Amp is passing through the controller 16 watt of heat is produced in the controller As more heat is produced the temperature inside the controller...

Page 22: ...rmation will also help you to manage the heat Place the controller in the right place The SSR of Auber WS series controller is mounted in the bottom of chassis The chassis is made of 3 mm thick alumin...

Reviews: