Assembly, installation and operating instructions
21
A (Width of basic unit)
B (Distance of suspen-
sion points)
C (Rear wall)
D (Outlet opening)
Model 61
625 mm / 24,6 inch
560 mm / 22 inch
590 mm / 23,2 inch
431 mm / 17 inch
Model 63
925 mm / 36,4 inch
860 mm / 33,9 inch
890 mm / 35 inch
731 mm / 28,8 inch
Model 66
1375 mm / 54,1 inch
1310 mm / 51,6 inch
1340 mm / 52,8 inch
1181 mm / 46,5 inch
Model 67
1725 mm / 67,9 inch
1660 mm / 65,4 inch
1690 mm / 66,5 inch
1531 mm / 60,3 inch
Tab. 5: Dimensions of basic unit
Note the Venkon minimum clearances when installing the basic units!
Highlight the dimensions and clearances of the key holes on the wall or ceiling as per the table, drill the holes and use
appropriate fixing materials to install the basic unit.
Align the basic unit for correct operation. Install the basic unit with a gradient on the condensation discharge side should
condensation be produced.
Once the basic unit has been aligned, prevent the fixing material from coming loose.