Venkon XL
Beschreibung
Assembly, installation and operating instructions
26
6.5.4 Condensation connection
6.5.4.1
Condensation drain with natural gradient
It is essential that a condensation drain is connected and appropriate fixed to a Venkon condensation drain connector (drain
size 15 mm). Ensure that the gradient is at least 1 cm/m, without restrictions and without rising sections of pipe (in accord-
ance with DIN EN 12056: formerly DIN 1986-100) to ensure the drainage of condensation from the basic unit. Take into ac-
count all applicable regulations, such as the use of a ball trap, when connecting the condensation line to the sewer system.
Protect the trap from drying out. The suction effect of the fan on the condensation drain neck could otherwise produce
troublesome odours. Consider using water vapour-impermeable insulation depending on the pipe material used for the con-
densation drain. You will need a condensation pump (optional accessories) should a natural gradient be impossible on site.
This is used to pump the condensation into higher collection or drainage equipment.
Condensation drains
Connect a trap to all existing condensation drain spigots.
Ensure adequate sealing water height (Hs).
Fig. 19: Sealing water height
Sealing water height:
Hs = H + 50 mm
H = static negative pressure in the unit (mm head of water)
(1 mm head of water = 9.81 Pa)
Minimum sealing water height Hs = 60 mm
Summary of Contents for Venkon XL
Page 2: ......
Page 5: ...5 13 2 ERP Datenblatt Venkon XL 70...
Page 67: ...Venkon XL Beschreibung Assembly installation and operating instructions 67 13 Certificates...
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ...www kampmanngroup com hvac products fan coils venkon xl 02 20 ENSAP Nr 1374732...