Tandem door air curtains
Door air curtains with patented Tandem technology
Assembly, installation and operating instructions
56
Parameter
Function
Standard
Min.
Max.
Unit
Door air cur-
tain
2
P116
reserved
-
-
-
-
-
P117
Lock function buttons on KaController
0
0
7
-
0
P118
On delay time
0
0
255
sec
10
P119
Off delay time
0
0
255
sec
30
P120
reserved
-
-
-
-
-
P121
reserved
-
-
-
-
-
P122
Relative fan speed increase via contact
2
0
5
-
2
P123
Maximum valve running time
150
0
255
sec
150
P124
Minimum P + I output variation for valve motion (0 to 10)
5
0
100
%
5
P125
reserved
-
-
-
-
-
P126
Weeks of operation
0
0
255
week
0
P127
Info weeks of operation reached (filter message)
0
52
255
week
0
P128
Reset weeks of operation
0
0
1
-
0
P129
Fan speed limiter activation in certain operating modes
0
0
1
-
0
P130
Absolute fan speed increase via contact
2
0
5
-
4
P131
External ventilation, delay time
0
0
255
min
0
P132
Operating level, master password
22
0
255
-
22
P133
Hysteresis for outside temperature to switch between heat-
ing/fan mode
0
0
255
K/10
0
P134
Threshold for outside temperature to switch between heat-
ing/fan mode
0
0
50
°C
0
P135
Enable virtual sensor
0
0
1
-
0
P136
Enable external ventilation
0
0
2
-
0
Tab. 12: Key parameters, standard revision 1.024 from 01.05.2018
12.2 KaController parameter list
Para-
meter
Function
Standard
Min.
Max.
Unit
Comment
t001
Serial address
1
0
207
-
Address in Mod-
bus network
t002
Baud rate
0 = Baud rate 4800
1 = Baud rate 9600
2 = Baud rate 19200
2
0
2
-
t003
Background lighting function
0 = Slow fade in, fast fade out
1 = Slow fade in, slow fade out
2 = Fast fade in, fast fade out
0
0
2
-
t004
Strong background lighting
4
0
5
-
t005
Sensor calibration of KaController sensor
0
60
60
°C
t006
LCD display contrast
15
0
15
-
t007
BEEP setting
0 = BEEP ON
1 = BEEP OFF
0
0
1
-
t008
Password for KaController Parameter menu
11
0
999
-