background image

27

Katherm QK nano – 

Ultra-small trench heater with EC tangential fan 

 

 

4.42

Ready-to-install convector-based floor trenches

 Assembly and installation instructions

LCD display symbols

1

Display of setpoint room temperature

2

Current time

3

Timer program enabled

4

Weekday 

5

Alarm 

6

Selected function is locked

7

Eco mode 

8

Setpoint setting enabled

9

Fan control setting Auto-0-1-2-3-4-5

10

Ventilation mode

11

Cooling mode

12

Heating mode

13

Automatic Heating/Cooling changeover mode

Operation of the basic functions

Function

Description

Switch On/Off

Switch on by pressing key 2 or the navigator dial. When switched on, the display shows a temperature. Switch off 
by pressing button 2 or the navigator dial. OFF is shown.

Change temperature

Turn the navigator dial to the left to lower, and to the right to raise, the required temperature. Confirm the entry 
by pressing the navigator dial.

Fan speed

Change by pressing the side fan button or using the navigator dial. Briefly press the navigator dial once. Turn the 
navigator dial to the left to lower, and to the right to increase the required fan speed. Press the navigator dial 
once more to confirm the display. 
In Automatic mode, the speed is adjusted when the room temperature deviates from the setpoint temperature.

Heating/Cooling/
Recirculation

Change by pressing the side fan button or using the navigator dial. 
To change using the navigator dial, first press the navigator dial for approx. 1 second to move to the Fan stage 
selection. Then press the navigator dial once again for 3 seconds to go to the Time setting. Press again for approx. 
3 seconds to move to the Timer menu. Press again for approx. 3 seconds to move to the Mode menu. Press briefly 
to confirm the entry.

Timer program

The KaControl provides the option of setting a weekly timer. Refer to the separate KaControl instructions for this.

9

10

11

12

13

1

2
3
4
5

6

7

8

Summary of Contents for Katherm QK nano

Page 1: ...nano Ultra small trench heater with EC tangential fan Assembly and installation instructions Keep these instructions in a safe place for future use I529 09 18 EN I SAP Nr 1254735 Kampmann de installat...

Page 2: ...s information can lead to serious personal injuries or damage to property by electrocution Carefully read these instructions in full prior to any assembly and installation work Anyone involved with th...

Page 3: ...6 3 Scope of delivery 7 4 Levelling 7 5 Water connection 8 6 Screeding 9 7 Connection openings Pipe openings 10 8 Number of height adjustment feet and raised floor feet 12 9 Maintenance 12 10 Electric...

Page 4: ...deemed to include compliance with the installation instructions described in these instructions The installation of this product requires specialist knowledge of heating cooling ventilation and elect...

Page 5: ...ctivity 1 S cm 700 Oxygen content O2 mg l 0 1 Hardness dH 4 8 5 Sulphur ions S not measurable Sodium ions Na mg l 100 Iron ions Fe2 Fe3 mg l 0 1 Manganese ions Mn2 mg l 0 05 Ammonia ions NH4 mg l 0 1...

Page 6: ...Disconnect all parts of the system that are being worked on Ensure that the system cannot be accidentally re connected Before commencing installation maintenance work wait until the fan has come to a...

Page 7: ...the window side Caution The height adjustment feet are already fitted to the floor trench They are fixed the wrong way round for transport reasons To install and adjust the height of the trench loosen...

Page 8: ...ories until tight onto the convector connections Then fit the flow and return pipes Perform a pressure test Adhere these installation instructions very visibly to the trench heater for subsequent trad...

Page 9: ...e grille sound insulation not with raised floors is fitted underneath the trench heater there are no sound bridges to the concrete slab especially close to the height adjustment feet appropriate mater...

Page 10: ...QK nano 24 V electromechanical 1 Flow 2 Return 3 Pipe openings 4 Cable openings 5 Terminal strip Room side connection Connections 1 2 female same end lef Room side Top view without cover panel Front...

Page 11: ...the convector Katherm QK nano KaControl or 230 V electromechanical model Model Katherm QK nano KaControl or 230 V electromechanical model 1 Flow 2 Return 3 Pipe openings 4 Cable openings 5 Power suppl...

Page 12: ...ct Katherm QK nano units to ensure their proper function and performance Fan Inspect the tangential fans every 6 months for dirt and damage visual inspection Clean the fan shafts carefully with a clot...

Page 13: ...applicable VDE and EN guidelines as well as Technical Wiring Regulations stipulated by the regional energy supply companies Only connect the unit to fixed cables Only use the room or clock thermostat...

Page 14: ...ple of 24 V electromechanical 44217072211124 Ask a qualified electrician to determine the type of cable and cable cross sections the cable cross sections basically depend on the fuses for the cable le...

Page 15: ...classes as accessories for the voltage supply 24 V DC The fan automatically switches off in the event of a motor fault Cabling BMS control Lay shielded cables e g IY ST Y 0 8 mm separately from high...

Page 16: ...W2 Voltage supply and control signal for fan and actuator W3 Voltage supply On site fuse central voltage supply 24 VDC Clock thermostat type 30456 actuator type 146906 terminal box on site Trench hea...

Page 17: ...the continuously variable parallel control of max 10 Katherm QK nano 230 V electromechanical models room temperature and fan presetting using dials temperature setting range 5 30 C IP30 rated voltage...

Page 18: ...supply W2 Control signal for fan and actuator W3 Operating mode changeover optional Subject to technical modifications Refer to the control accessory documentation in the event of deviation from the...

Page 19: ...Description of control Basic settings The KaControl version provides the option of controlling Katherm QK nano units by means of a control unit supplied separately or on site building management tech...

Page 20: ...ry and can be used as a changeover sensor If used set the DIP switch to ON No clip on sensor fitted OFF 4 Heating Cooling External changeover ON ON If the function is activated the operating mode of t...

Page 21: ...onnect the bus lines when the unit is fully disconnected DIP switch setting The DIP switches on the rear of the KaController should be set as per the adjacent figure DIP switch no 1 ON DIP switch no 2...

Page 22: ...FF changeover KaController 24 V Typ 3210001 oder Typ 3210002 Netz 230 VAC Absicherung bauseits 3 W1 W2 W3 W4 W4 W5 W5 2 2 3 3 3 2 3 W1 3 3 3 2 Externer Kontakt Ein Aus optional Funktion parametrierbar...

Page 23: ...ble length 10 m W5 Control signal for fan and actuator total maximum cable length 10 m W6 Bus signal tLan Subject to technical modifications Refer to the control accessory documentation in the event o...

Page 24: ...wer 230 VAC Fuse by others Lay shielded cables e g IY ST Y 0 8 mm separately from high voltage cables Lay shielded paired cables e g CAT5 AWG23 of at least the same value separately from high voltage...

Page 25: ...o 1 230 V KaControl Trench heating Katherm QK nano Unit no n 230 V KaControl Automation station RI 20 KOhm RI 20 KOhm RI 20 KOhm Lay shielded paired cables e g CAT5 AWG23 of at least the same value se...

Page 26: ...ne with side keys and one without Both control units can be used to call up all functions with the keys offering the possibility of quick access to some functions No Description 1 Display of the opera...

Page 27: ...nfirm the entry by pressing the navigator dial Fan speed Change by pressing the side fan button or using the navigator dial Briefly press the navigator dial once Turn the navigator dial to the left to...

Page 28: ...ieb 20 C Trockenkugel Sound power test At ambient conditons without water flow Test Schallleistungspegel Bei Umgebungsbedingungen ohne Wasserdurchsatz Contact Details Kampmann GmbH Kontaktinformatione...

Page 29: ...29 Katherm QK nano Ultra small trench heater with EC tangential fan 4 42 Ready to install convector based floor trenches Assembly and installation instructions...

Page 30: ...30 4 42 Katherm QK nano Ultra small trench heater with EC tangential fan Ready to install convector based floor trenches Assembly and installation instructions...

Page 31: ...31 Katherm QK nano Ultra small trench heater with EC tangential fan 4 42 Ready to install convector based floor trenches Assembly and installation instructions...

Page 32: ...ann GmbH Friedrich Ebert Str 128 130 49811 Lingen Ems Germany T 49 591 7108 660 F 49 591 7108 173 E export kampmann de W Kampmann eu Kampmann UK Ltd Dial House Govett Avenue Shepperton Middlesex TW17...

Reviews: