KaDeck
Assembly, installation and operating instructions
29
7
Electrical connection
IMPORTANT NOTE!
Condensation formation in the cooling unit!
In the event of on-site valve control, the cooling valve must be closed when the fans are switched off.
7.1
Maximum electrical rating values
KaDeck, electromechanical version (*00)
Article
number
Nominal voltage [V
DC]
Mains fre-
quency [Hz]
Nominal power
[W]
Nominal
current
[A]
Ri analogue
input [kΩ]
IP class
Protection
class
3261xxx11x
xx
230
50
16
0.13
100
IP20
I
3261xxx61x
xx
230
50
24
0.20
100
IP20
I
3261xxx12x
xx
230
50
27
0.22
50
IP20
I
3261xxx62x
xx
230
50
35
0.29
50
IP20
I
Tab. 6: Maximum electrical rating values KaDeck
KaDeck, KaControl version (*C1)
Article
number
Nominal voltage [V
DC]
Mains fre-
quency [Hz]
Nominal power
[W]
Nominal
current
[A]
Ri analogue
input [kΩ]
IP class
Protection
class
3261xxx11x
xxC1
230
50
18
0.15
20
IP20
I
3261xxx61x
xxC1
230
50
26
0.22
20
IP20
I
3261xxx12x
xxC1
230
50
29
0.24
20
IP20
I
3261xxx62x
xxC1
230
50
37
0.31
20
IP20
I
Tab. 7: Maximum electrical rating values KaDeck