 4. Accessories

External temperature sensor KF-2 (sleeve sensor) or BTF2-C47-0000 (surface-mounted 

room sensor)

 5. Technical data

Operating and switching voltage:

230VAC / 50Hz

Outputs:

Relay NO contact max. 5(1)A / 250V~, type 1.B,

analogue output 0-10V (SELV), max. 5mA for fan control

Step switch fan:

3-step switch 1.8V, 4V, 6V (factory setting),

each +/- 1.5V adjustable

Operating mode switch:

Standby (frost protection),manual fan operation,

Automatic fan operation

Control range:

22 … 30°C

Switching differential:

0.5K with temperature change of 4K/h

Proportional band fan:

adjustable 0.5...3K (factory setting 1.5K)

ECO temperature differential:

1 ... 6K (factory setting 2K) Sensor

Tolerance internal sensor: 

approx. 1K

Frost protection temperature:

approx. 5°C

Switching differential

frost protection:

approx. +1K

Power consumption:

< 1W / < 2VA

Protection class:

II, nach entsprechender Montage

Degree of protection:

IP30, nach entsprechender Montage

Permissible ambient temperature:

0 … 40°C

Storage temperature:

-20 … 70°C

Permissible humidity:

max. 95%r.H. non-condensing

Mounting:

on wall or flush-mounted box Housing

Housing material and colour:

ABS plastic, pure white similar to RAL9010

Features:

Operating mode switch Off / Manual / Automatic, 

3-stage fan switch, mechanical range limitation of the 

setpoint adjuster, internal DIP switches for function 

selection, three-colour backlit setting marker, side 

button for activating and ending the parameter setting

Degree of contamination:

2

Rated impulse voltage:

4.000 V

Energy efficiency class:

I (contribution to seasonal room heating energy 

efficiency 1%)

 6. Sensor table (characteristic curve) for external sensors

The sensor table applies to the optional external temperature sensor. Sensor „2“ – NTC 47

Sensor temperature [°C]

Resistance value [kOhm]

-10

264,028

0

155,480

10

94,377

15

74,314

20

58,910

25

47,000

30

37,732

40

24,750

50

16,597

 7. Connection and dimensional drawings / position drawing dip

  switches S1 to S4

int.sensor

ext.sensor

electronics

ECO contact

antifreeze contact

S1

S2

NTC 47K

N

N

N

L

S1-4

Supply

+

-

Safety extra low voltage (SELV)

turn-off delay

S4

NC

C

NC

NC

no turn-off delay

Attention!

If the external 

contact input at 

terminals 13 and 14 

is not the terminals 

must be connected 

with a wire jumper. 

(jumper is set in the 

asdelivered state)

Attention! 

Partition 

wall for safe 

separation between 

mains voltage and 

protective low voltage 

mount accordingly.

Switch S1 - S4

Switches

ON

OFF

S1

Contact terminal 13 and 

14 Function ECO

Contact terminal 13 and 14 

Function OFF (frost protection)

see point 2.5

S2

Fan off when

output inactive

Fan switch-off delay

10 minutes

see point 2.4

S4

Internal sensor

Terminals 7 and 8

external sensor

see point 2.3

 8. Warranty

The specified technical data were determined by us in a suitable test environment (we will 

provide information on this on request) and only represent the agreed quality on this basis. 

The client/customer is responsible for checking the suitability for the purpose intended by 

the client/customer or the use under the specific conditions of use; we do not assume any 

warranty for this. Subject to change without notice.