Set the pump to normal re-circulation mode, then with the unit 
running, add the corrosion inhibitor to the reservoir. Allow the 
chemical  to  circulate  through  the  system  for  about  10  minutes, 
reversing direction occasionally.

Switch the pump off and unplug it from the power supply.
Disconnect all hoses from the pump and the heating system.

Empty the pump tank of any remaining water. If the system is 

vented, the residual water (which may contain some corrosion 

inhibitor) may be poured into a bucket and added to the F&E 

tank after this has been cleaned.

Reconnect any removed radiator or disconnected boiler or 

pump. Reset radiator valves to original settings. Remove any 

temporary isolating valves or caps on expansion and cold feed 

pipes, and restore non return valves to normal operation if 

necessary. The feed and expansion tank should be thoroughly 

cleaned and disinfected before placing into service again.

Page 4

Before you leave

Re-instating the system

6. Set Clearflow into circulation mode, with full flow 

through whole heating system

(all radiator valves open).

Add Systemsafe-DM and circulate for 10 minutes 

before disconnecting Clearflow and restoring system 

to normal operation. B

leed all radiators.

Now dump on the same radiator in the 

opposite direction,until water runs clear. Close the 

radiator trapping the fresh water.

5. Start dumping. Adjust inlet water to ensure tank 

water level remains constant. Allow to run until 

dump water is clear.

After circulating through last radiator,

switch to dumping on that one radiator, 

until water runs clear.

4. Switch on Clearflow pump, and circulate for 10 

minutes, reversing flow regularly.

Shut off first radiator, and move to second. Work 

around system, putting full flow through 

each radiator in turn.

Test that dump water is neutral 

with either pH paper or electronic 

pH meter.

3. Open all radiator and lock-shield valves, and set 

zone valves to manual position, for full flow 

hroughout system.

Shut off all radiator valves except for one radiator. 

Allow full flow through this radiator for 5 minutes, 

reversing flow regularly.

Commence final dump procedure, 

with all radiators wide open. Allow 

to run until dump water is clear.

2. Connect Clearflow pump into heating system. 

Connect dump, water inlet, and overflow hoses to 

Clearflow pump.

Continue circulation through wide open system for 

fifteen minutes, reversing flow regularly.

Add 100gm of Neutralising 

Crystals to tank, and circulate

for 10 minutes.

1. I

f system is vented, cap off the cold feed and 

expansion pipe.

If possible, switch on boiler to heat water to 50oC.

Don’t leave boiler firing continuously.

Restore circulation through Clearflow pump 

and complete heating system

(all radiator valves open).

7. Pour 2.5 litres

PowerFlush FX2

 into Clearflow tank.

Open up previous radiator, and dump on that until 

water runs clear. Work around system in reverse, 

dumping through each individual radiator in turn.

7. Pour 500ml of

Hyper-Flush

into Clearflow tank.

EITHER.

EITHER.

When using

FX2

When  using 

Hyper- Flush

Quick guide to the power flushing procedure