5.2. PROGRAM STRUCTURE
Controller has 14 specific data zones; each zone is password protected.
Other than RUN and USER PASSWORDS, only authorized and trained personnel should have
access to other specific zones.
FUNCTION
PASSWORD
RUN
NO PASSWORD
USER
9999
MAINTENANCE
6842
5.2.1 Run menu
Press menu Press RUN PARA
MENU
VALUE
FUNCTION
Air Pressure
00.80MPa Display air pressure
Discharge
Temperature
000
75˚C
Display discharge temperature
System Pressure
00.75MPa Display system pressure
Oil Pressure
Differential
00.55MPa Display oil pressure differential
Front Rotor T
00
65˚C
Display front rotor temperature
Rear Rotor T
00
65˚C
Display rear rotor temperature
Oil Filter
0020H
Display Running Time of Oil Filter Element
Air/Oil Separator
0020H
Display Running Time of Air/Oil Separator Element
Air Filter
0020H
Display Running Time of Air Filter Element
Lube
0020H
Display Running Time of Compressor Lubricant
Grease
0020H
Display Running Time of Main Motor Grease
Serial Number
123456789 Compressor serial number
Drain Close Time (S)
0060
Time set for Condensate Drain to stay closed
Motor current
A: 000.0A
B: 000.0A
C: 000.0A
Display motor current
Fan current
A: 000.0A
B: 000.0A Display Fan current