OPzV Battery Operation Manual
11
Mon
thly Maintenance
Items
Details
Benchmarks
Maintenance
①
Total b
attery gro
up voltage
Use multi-meter
check total voltage
across positive and
negative terminal
1.The value of measured
and displayed on
equipment should be
close.
2. Voltage error after
compensation should be
less than ±50mV
Adjust the charging voltage to recom
mended range if there is a deviation;
Repair the equipment if voltage can’
t be adjusted.
②
Battery
appearan
ce
Bulge, leakage
or damage
Appearance should be
OK
Replace the battery if bulge, leakage
or damage
Dust, dirty
Clean
Cleaning
Connectors,
terminals
No rust
Clean and anti rust dealing
③
Battery
surface te
mperature
Use infrared
thermometer
measure surface
temperature
Less than
Further check and analysis if high
temperature found
Quarterly Maintenance
Yearly Maintenance
Items
Details
Benchmarks
Maintenance
Items
Details
Benchmarks
Maintenance
①
Float
voltage
for each
battery
Measure the voltage of
each battery under floatin
g, using a meter with four
and half digits.
Voltage difference
less than
2V: 90mV
6V: 240mV
12V:480mV
If there is a deviation, discharge the
batteries and perform a equalizing ch
arging, observe for one through two
months under floating. Contact us if
no improvement.
②
Correct
the
low
voltage
batteries
If more than two cells’
voltages are less than
2.16V/cell after
temperature adjustment,
the batteries need
equalization charging.
Float voltage
≥
2.16V/cell
If battery float voltage less than
2.16V/cell after equalization charge,
the battery need do a 80% capacity
test.
③
Activated
discharge
Perform a discharge-char
ge cycle, using lower
level of equalizing charge
voltage for the charge.
Discharge around
30% of the
nominal capacity.
Perform the discharge-charge cycle if
no power-off for six months.