1 7
Settings
–
Inductive penalty limit ( % 3 – 50 )
6
This is the section in which the limit value of inductive/active % acceptable in compensation, is
entered. This value is determined by electric distribution company and is recommended to setup a
value slightly lower than requested to avoid penalty. The value is setup to the required step by
using up and down keys starting from the digit where the blue line is. Then, left key is pressed
and the blue line moves next to left digit. All values are entered in the same way by using the up
and down keys.
Press “Apply” key inorder to take the inductive penalty line into memory. “Save changes” message
will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
Enter inductive penalty limit
2 3
5 6
8 9
11 12
7
4
1
10
30
Apply
▲ +
▼ -
◄
%
20
Enter inductive penalty limit
2 3
5 6
8 9
11 12
7
4
1
10
30
Cancel
Okay
Exit
%
20
Save
changes
1 7
Settings
–
Capacitive penalty
limit ( % 3 – 50 )
7
This is the section in which the limit value of capacitive/active % acceptable in compensation, is
entered. This value is determined by electric distribution company and is recommended to setup a
value slightly lower than requested to avoid penalty. The value is setup to the required step by
using up and down keys starting from the digit where the blue line is. Then, left key is pressed
and the blue line moves next to left digit. All values are entered in the same way by using the up
and down keys.
Press “Apply” key inorder to take the capacitive penalty line into memory. “Save changes”
message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
Enter cap.penalty limit
2 3
5 6
8 9
11 12
7
4
1
10
30
Apply
▲ +
▼ -
◄
%
10
Enter cap.penalty limit
2 3
5 6
8 9
11 12
7
4
1
10
30
Cancel
Okay
Exit
%
10
Save
changes
1 7
Settings
–
Current Transformer (Primary) value
( 5.......10000 / 5A )
8
Enter current transformer value
2 3
5 6
8 9
11 12
7
4
1
10
30
Apply
▲ +
▼ -
◄
00500
/ 5A
Enter current transformer value
2 3
5 6
8 9
11 12
7
4
1
10
30
Cancel
Okay
Exit
This is the section in which the primary value of current transformers in compensation system, is
entered. The value is setup to the required step by using up and down keys starting from the digit
where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All
values are entered in the same way by using the up and down keys. Press “Apply” key inorder to
take the current transformer (primary) value into memory. “Save changes” message will appear
on the screen. When “Okay” key is pressed, the value is taken into memory.
00500
/ 5A
Save
changes
1 7
Settings
–
Number of Steps ( 3 – 12 )
9
Enter number of steps
2 3
5 6
8 9
11 12
7
4
1
10
30
Apply
▲ +
▼ -
◄
2 3
5 6
8 9
11 12
7
4
1
10
30
Cancel
Okay
Exit
This is the section in which the number of steps will be used for compensation, is entered. The
value is setup to the required step by using up and down keys starting from the digit where the
blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are
entered in the same way by using the up and down keys. Press “Apply” key inorder to take the
number of steps into memory. “Save changes” message will appear on the screen. When “Okay”
key is pressed, the value is taken into memory.
12
12
Save
changes
14
Enter number of steps