Page 10
Installation instructions Powador 3200 / 4400 / 5300 / 5500 / 6600_EN
– The heat sink may reach a max. temperature of 90°C.
Therefore, mount the inverter only on walls made from
heat-resistant material.
– Ensure that the wall has adequate load-bearing capacity and
use appropriate installation material.
– Be sure to install the inverter in a suffi ciently elevated place,
especially in areas prone to fl ooding.
– Installation at eye level makes it easier to read the display.
IMPORTANT
Due to the high system voltage, the current that fl ows on
the DC side is lower than that fl owing on the AC side. This
means that losses on the AC-side lead are higher than those
on the DC-side lead at identical cable cross-sections. For this
reason and due to thermal factors, it makes sense to position
the inverter near the counter.
5.2 Installing the inverter
Notches for mounting
the Powador
M5 screw
Fixing
Figure 5.1:
Powador wall bracket
An installation kit consisting of four fi xings and four 70 mm Spax
screws is supplied with the inverters. Check the composition
and condition of the wall before installation. If necessary, use
an installation kit other than the one supplied with the inverter.
ACTION
– Drill the holes for the fi xings at the selected installation
position to match the cut-outs in the mounting plate.
– Place the fi xings into the holes.
– Use the Spax screws to mount the wall bracket onto the
wall at the selected location. When doing so, be sure that
the arrow cut into the mounting plate points upwards
– Mount the inverter on the mounting bracket so that the
pegs in the heat sink rest in the notches
– Lock the safety catch. To do this, slide the upper end of
the safety catch towards the wall until the groove runs
parallel to the wall (see fi gure 5.3).
Figure 5.2:
Safety catch
(open)
Figure 5.3:
Safety catch (closed)
S e c t i o n 5 ·
I n s t a l l a t i o n a n d S t a r t - U p