![Kaco Powador 30.0-72.0 TL3 Manual Download Page 58](http://html1.mh-extra.com/html/kaco/powador-30-0-72-0-tl3/powador-30-0-72-0-tl3_manual_3553855058.webp)
Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
1st node … 10th node
Voltage | Reactive
power | Excitation
0 – 100 [% S
max
]
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
Note: Storage inverters only for feed-in operation
0 – 100 %
cos ϕ of the node
Over-excited | under-
excited
Reactive power mode Under-excited relates to inductive load, over-ex-
cited relates to capacitive load.
Q(U) 10 nodes
Lock-in power
0 – 100 [% S
max
]
Power threshold, function is activated if limit value is exceeded.
Lock-out power
0 – 100 [% S
max
]
Power threshold, function is activated if limit value is undershot.
Lock-in time
0 – 60 [s]
Length of time that the active power must remain below the lock-in
power level before control is deactivated.
Lock-out time
0 – 60 [s]
Length of time that the active power must remain below the lock-out
power level before control is deactivated.
Settling time
1 – 120 [s]
Settling time in the event of an abrupt change in the reactive power tar-
get value (e.g. caused by a voltage jump). The transient behaviour cor-
responds to a first-order filter (PT-1) with transient time = 5 Tau.
NOTE: The settling time is overlaid with the increasing and decreasing
gradient.
4
1
2
3
4
Downtime
0-10000 [ms]
If the voltage switches from a characteristic curve section with Q=0 to a
characteristic curve section with Q≠0 under active control, then the re-
active power setting process is delayed by the set dead time. Once the
dead time has expired, the control circuit is no longer subject to a delay
and the set transient time determines the transient behaviour.
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decreas-
ing
In addition to configuring the dynamic behaviour using the transient
time corresponding to a first-order filter, the reactive power setting can
be determined by a maximum gradient - this means the maximum
change in the reactive power per time period.
1 – 60000 [% S
max
/
min]
Maximum change in the reactive power %S
N
/min in the event of a
change to over-excited mode
NOTE: The gradient is overlaid with the settling time.
Min. cos-phi Q1 - Min.
cos-phi Q4
In the event of a significant voltage deviation, the maximum reactive
power adjustment range can be limited by a minimum cos ϕ in order to
prevent an excessive reactive power supply and, as a result, a significant
reduction in the maximum active power that can be fed in.
Q1
Minimum cos ϕ in over-excited operating mode (in-feed).
Q4
Minimum cos ϕ in under-excited operating mode (in-feed).
Q2
Minimum cos ϕ in over-excited operating mode (charge).
Q3
Minimum cos ϕ in over-excited operating mode (charge).
Priority mode
Q priority | P priority
P priority can be selected as an alternative to the standard setting Q pri-
ority. When it comes to P priority, the reactive power adjustment range
is limited subject to the limited apparent power of the inverter and the
active power that is currently available and fed in.
Powador 30.0-72.0 TL3
Page 58
EN