4
1
2
3
Power reduction P(f)
NOTE: The unit supports the internal power factor correction after
P(f).
1 Open the menu: Press the
Right arrow button
or
Enter
button
.
Note: All the parameters are configurable here and via the WEB in-
terface
Configuration via web user interface [See sec-
Not for IL,
IT
4
1
2
3
4
P(f) operation mode
Off | Mode 1 | Mode 2
NOTE: More detailed information can be found in
F
Specify the operation mode.
4
1
2
3
4
Threshold activated
45 Hz – 70 Hz
F
Specify activation threshold (if mode 1 or mode 2 is active, this menu
option is displayed permanently for IT and IL!)
NOTE: The function is activated if the activation threshold is exceeded.
In mode 2 this value also serves as a deactivation threshold.
4
1
2
3
4
Threshold deactivated
Min. 45 Hz – 61,5 Hz
Max. 45 Hz – 70 Hz
NOTE: If the grid frequency is within the deactivation range for the
duration of the deactivation time, then the function is deactiv-
ated.
1 Specify deactivation threshold (if mode 1 or mode 2 is active, this
menu option is displayed permanently for IT and IL!).
Not for IL,
IT
4
1
2
3
4
Deactivation time
F
Specify time for power reduction (if mode 1 is active)
4
1
2
3
4
Gradient
F
Set gradient of power limitation function with increasing frequency
in % / Hz. The percentage value is based on the rated frequency (if
mode 1 or mode 2 is active, this menu option is displayed perman-
ently for IT and IL!)
4
1
2
3
4
Intentional delay
F
Set the power limitation delay in seconds (if mode 1 or mode 2 is act-
ive; this menu option is displayed permanently for IT and IL!).
4
1
2
3
4
Settling time
F
Set the power reduction delay in seconds (if mode 1 or mode 2 is act-
ive; this menu option is displayed permanently for IT and IL!).
4
1
2
3
4
Rise Outg. grad. & Fall.
Outg. grad.
F
Specify output gradient increase and decrease in
0
/
00
(per thousand).
4
1
2
3
4
Deact. grad.
F
Specify deactivation gradient in
0
/
00
(per thousand) /minute (if mode "1" or mode "2" is active. This
menu option is displayed permanently for IT and IL!).
4
1
2
3
Fault ride-through
NOTE: The device supports dynamic grid stabilization (Fault Ride-
Through).
F
Further parameterisation is possible via the web interface
4
1
2
3
Reactive power
1 Open the menu: Press the
Right arrow button
or
Enter
button
.
2 Activating reactive power process: Select process a press the
Enter button
. The active process is highlighted.
4
1
2
3
4
cos-phi const.
1- 0.3
More detailed information about the procedure can be found at:
1 Reactive power control [See section 10.1
2 Determine the specified displacement factor.
Over-excited | under-
excited
F
If a power factor not equal to 1 is selected: Select the type of phase
shift: under-excited (inductive load), over-excited (capacitive load).