Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Default gateway
F
Enter IPv4 address of the gateway.
4
1
2
3
4
DNS server settings via
DHCP
Status
F
Activate or deactivate the DNS server from the DHCP.
On: Once the DHCP server becomes available, the IP address is automat-
ically applied and the aforementioned menu items are filled in.
Off: Apply settings manually.
4
1
2
3
4
Primary DNS &
Secondary DNS (op-
tional)
1 Enter IPv4 address of DNS server.
2 Confirm the action field.
4
1
2
3
4
Web Settings
NOTE: Opportunity to set up the http ports.
HTTP Port
F
Set up the port at which the webserver can be reached.
HTTPS Port
1 Set up the safe port at which the webserver can be reached.
2 Confirm the action field.
4
1
2
3
4
Modbus
NOTE: Option to set the Modbus port.
4
1
2
3
4
Port
F
Set up network port.
4
1
2
3
4
Activation
Status
F
Allow Modbus TCP read access.
4
1
2
3
4
Write access
Status
F
Allow Modbus TCP write access.
Enabling the write access allows system critical settings to be changed
over Modbus TCP. Really enable write access?
F
Confirm the action field.
4
1
2
3
4
MQTT
NOTE: The MQTT protocol is used to implement the advanced func-
tions between the Segment Controller and the inverter (in particular,
firmware updates, distribution of device configurations etc.).
Broker IP
1 Displays the IP address transmitted by the Segment Controller.
NOTE: The standard settings allow for successful communication
with the Segment Controller.
2 Confirm the action field.
Broker port
4
1
2
3
4
RS485
NOTE: Opportunity to parameterize the RS485 interface. The parame-
ters of the RS485 (CON901) are (as with all KACO inverters): 9600
baud, 8n1 and cannot currently be re-configured on the web interface
RS485 address
NOTE: The address must not be the same as that of any other device
or a data logger.
F
Assign a unique RS485 bus address to the device.
Bus termination is carried out on the HMI board by means of a dip-
switch
F
Confirm the action field.
4
1
2
3
4
Power Control
Input screens for power regulation
4
1
2
3
4
Power limitation
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power by the internal power
limitation. This may be necessary in order to limit the maximum
power rating of the plant at the grid connection point, upon the grid
operator's request.
4
1
2
3
4
Internal
NOTE: Opportunity to limit the power internally
Power limitation
Status
F
Specify the activation status.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 56