Maintenance/Troubleshooting
Operating Instructions KACO blueplanet 29.0TL3
Page 59
EN
Status
Display
Explanation
Action
OS
61
External
limit (%)
The external limit
Power control
was activated by the grid operator.
The inverter limits its power.
OS
63
Measured values
P(f )/frequency-dependent power reduction: Frequency-depend-
ent power reduction will be activated when the BDEW (German
Association of Energy and Water Industries) Medium Voltage
Directive goes into effect. Power reduction starts at a frequency of
50.2 Hz.
OS
64
Measured values
Output current limiting: The AC current is limited once the speci-
fied maximum value has been reached.
FS
67
Fault
at power section 1
There is a fault in the power sec-
tion.
"
Notify your author-
ised electrician.
E
FS
70
Fan error
The fan is malfunctioning.
"
Replace
defective fan.
E
FS
73
Standalone grid err.
Standalone mode was detected.
-
-
OS
74
External idle power
requirement
The grid operator limits the feed-in
power of the inverter via the trans-
mitted reactive power factor.
-
-
OS
79
Insulation measure-
ment
Insulation measurement in pro-
gress on the PV generator.
-
-
FS
80
Insulation meas. not
possible
The insulation measurement
cannot be performed because the
generator voltage is too volatile.
-
-
FS
81,
82,
83
Protection shutdown
line volt.
L1, L2, L3
Overvoltage has been detected on
a conductor. An internal protec-
tive mechanism has disconnected
the device to protect it against
damage.
"
In case of repeated
occurrence:
Notify your author-
ised electrician!
E
FS
84
Protection shutdown
undervolt. DC link
A voltage deviation has been
found in the DC link. An internal
protective mechanism has dis-
connected the device to protect it
against damage. In a TN-C-S grid,
the PE must be connected to the
device and at the same time the
PEN bridge in the inverter must be
removed.
"
In case of repeated
occurrence:
Notify your author-
ised electrician!
E
FS
85
Protect. shutdown
overvolt. DC link
E
FS
86
Protection shutdown:
DC link asymmetry
Overvoltage has been found in
the DC link. An internal protec-
tive mechanism has disconnected
the device to protect it against
damage.
"
In case of repeated
occurrence:
Notify your author-
ised electrician!
E
FS
87,
88,
89
Protection shutdown
overcurrent
L1, L2, L3
A current that has been found on a
conductor is too high. An internal
protective mechanism has dis-
connected the device to protect it
against damage.
"
In case of repeated
occurrence:
Notify your author-
ised electrician!
E
FS
93,
94
Self test error Buffer 1,
Buffer 2
The control board is defective.
"
Notify authorised
electrician / KACO
Service!
E/K
Table 8:
Operating status and fault messages on the display