INSTALLATION GUIDE

Remote Access Controller Model 3.5

with KIM Swipe Reader

Solitaire 710-II / 710 / System 700 / Generation E-760

PK2918

Summary of Contents for 3.5

Page 1: ...INSTALLATION GUIDE Remote Access Controller Model 3 5 with KIM Swipe Reader Solitaire 710 II 710 System 700 Generation E 760 PK2918 ...

Page 2: ...ccessories 9 Drilling Templates 11 Disclaimer Please read and follow all directions carefully These instructions are designed for use by maintenance professionals or lock installers who are familiar with common safety practices and competent to perform the steps described Kaba Ilco is not responsible for damage or malfunction due to incorrect installation however arising Carefully inspect windows ...

Page 3: ...ontrol panel should be securely screwed to the wall using the four mounting holes If possible the control panel should be mounted at a workable height with clearance to open the door com pletely Notes Access to control panel is restricted to service personnel only A certified electrician must connect the AC power to the Control Panel in accordance with applicable local standards Kaba Ilco is not r...

Page 4: ...e cable shield to the chassis ground connection at terminal TB6 on the Power Supply C 11 Install the diode across the terminals of the electromagnetic lock E or using the butt connectors provided in the Installation Kit install the diode across the two wires of the electric strike G Do not reverse diode polarity Note This step is not necessary if installing an HES 7000 Series electric strike or Ru...

Page 5: ...emplate for the Satin Chrome KIM Swipe Reader located at the end of this booklet mark the holes for the cable and screws 2 Wearing safety glasses drill the holes in the wall Enlarge the upper part of the cable hole 3 Tap the plugs into the wall then tighten the screws fully Undo the screws one turn leaving a small gap between the screw head and the wall 4 Fish the cable to the control panel and ma...

Page 6: ...tromagnetic Lock Electric Strike Note 1 Due to Hanchett Entry Systems HES modifying their 7000 series electric strikes and Rutherford Controls modifying their 83xx series electromagnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit ...

Page 7: ...eir 7000 series electric strikes and Rutherford Controls modifying their 83xx series electromagnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit Dual Reader Access Controller Assembly Electromagnetic Lock Electric Strike ...

Page 8: ...ccess Delay DIP Switch Settings S2 CFG 4 3 2 1 SEC 1 ON ON ON ON 8 2 ON ON ON OFF 1 3 ON ON OFF ON 3 4 ON ON OFF OFF 5 5 ON OFF ON ON 10 6 ON OFF ON OFF 15 7 ON OFF OFF ON 20 8 ON OFF OFF OFF 25 9 OFF ON ON ON 30 10 OFF ON ON OFF 35 11 OFF ON OFF ON 40 12 OFF ON OFF OFF 50 13 OFF OFF ON ON 60 14 OFF OFF ON OFF 90 15 OFF OFF OFF ON 120 16 OFF OFF OFF OFF REINIT Example of S2 Settings Delay times ca...

Page 9: ...nnector programming port P1 on the controller PCB in the control panel Refer to Figure 1 or Figure 2 for the positions of the J1 and P1 connectors Refer to Figure 4 or Figure 5 below for an illustration 2 For step by step programming instructions refer to chapter 5 of the Kaba Ilco Lodging Access Control System Reference Manual version 6 5 or higher Note When programming the RAC you do not swipe t...

Page 10: ...nce back up batteries should be replaced every 2 to 3 years and tested every 6 months by removing main AC power 4 4 Power Failure In the event of an electrical failure the system will revert to standby status for a period of 4 hours if the optional battery is installed If the electrical power is restored within three days the system will recover automatically and should require no additional progr...

Page 11: ...ng their 7000 series electric strikes and Rutherford Controls modifying their 83xx series electro magnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit NOTE 1 Due to Hanchett Entry Systems HES modifying their 7000 series electric strikes and Rutherford Controls modifying their 83xx series electro magnetic locks to include an on board d...

Page 12: ...with Timer NOTE 1 Due to Hanchett Entry Systems HES and Rutherford Controls modifying their electro magnetic locks to include an on board diode it is no longer necessary to install the diode from the installation kit For electric strikes it is still necessary to install the diode from the installation kit ...

Page 13: ...Installation Guide 11 Notes Drilling Templates for KIM Swipe Readers SATIN CHROME BLACK Drill 0 25 hole for cable 6 x 0 5 12 7 mm screw x4 4 x 0 125 3 175 mm hole 1 3 33 mm Back Panel of Reader ...

Page 14: ...ntréal QC H4P 2G7 Technical Support 1 800 906 4526 Customer Service T 1 877 468 3555 F 514 735 6589 General Information www kabalodging com Online Consumable Orders www keycard com To access all of our easy steps please visit our Support Website http connect kabalodging com ...