KK1 Pro Single Pump Controller 

5.0 Fault messages, possible malfunctions, and solutions 
 

Message 

on Display   

Possible cause 

Solution   

High level 
alarm   

1. The level floating switch 
does not work 
2. The set run time is too 
short 
3. The delay start time is 
too long   

1. Check the level floating switch, 
and remove any impurity if the 
switch is blocked; if the FS contact 
failed, replace the floating switch.   
2. Adjust the run time. 
3. Adjust the delay start time.   

No-load 

The set run time is too 
long   

Adjust the run time   

No-load 

The current is too large   

1. Check the pump and remove any 
impurities if winding onto the 
pump.   
2.Check the grid power supply and 
pump cable for electric leakage. 
3.Replace any damaged pump by a 
new one. 

Cycle times  1. The lower FS 

corresponding to the 
pump is always in the ON 
state. 
2. The set run time is too 
short. 
3. The floating switch fixed 
position is too low   

1. Check the level floating switch, 
and remove any impurity if the 
switch is blocked; if the FS contact 
failed, replace the floating switch.   
2. Adjust the run time. 
3. Adjust the FS position.   

In the 
pressure 
mode, the 
water level 
is displayed 
incorrectly 

1. Air leakage from air pipe   
2. When connecting air 
pipe, the end of the air 
vent is not immersed in 
water.   

1. Check each connection of air pipe 
for air leakage. 
2. Press the Manual button to drain 
the water level below the air intake, 
and release the Manual button. 

9

13

 

 

Patented products, protected by law

 

 

Summary of Contents for KK1 Pro

Page 1: ...hen Ltd Patented products protected by law K2K Technology Shenzhen Ltd Tel 0755 86329782 Fax 0755 86329783 Single Pump Controller KK1 Pro single pump controller 220V 380V Easy to use and simple to set...

Page 2: ...ecifications characteristics and optional modes of operation 3 2 1 Product specifications 3 2 2 Characteristics 4 2 3 Optional functions and components specially stated in the order if required 4 3 0...

Page 3: ...ding to the standard range given below Three phase AC 380V 4 5KW Max 12A Single phase AC 220V 2 2 KW Max 12 A 1 2 Qualification of personnel The personnel for installing initiating and maintaining the...

Page 4: ...f operation of the delivered product can only be granted when the product is used appropriately according to paragraph 1 1 of the operating manual The limiting values given in technical values have to...

Page 5: ...ctions and components specially stated in the order if required Level Flow Switch FS High Level FS Schneider Contactor Chint Contactor 3 0 Settings operational elements 3 1 Settings Through the Set bu...

Page 6: ...ual mode pump will stop automatically after 2 minutes to prevent dry run Alarm In case of fault alarm will work to issue a warning sound For High Level FS Alarm or High Level the alarm will disappear...

Page 7: ...the pump working current in real time Rat Current Rated current 1 0 20 0 A Set the rated current of the pump during normal operation Max Try run Non load run time 1 20 S The working current during the...

Page 8: ...le phase the Three phase or Single phase option is available for power supply Service mode OFF ON OFF ON ON Set all data OFF Only the set data can be displayed if not in the ON state converted to the...

Page 9: ...uage Available languages Available languages Chinese English or German language Alarm info Alarm information Include a High level alarm b Pump non load alarm Warning c Pump overload alarm d Pump cycle...

Page 10: ...heck the grid power supply and pump cable for electric leakage 3 Replace any damaged pump by a new one Cycle times 1 The lower FS corresponding to the pump is always in the ON state 2 The set run time...

Page 11: ...supply water pump and floating switch The electric connection must be carried out by the qualified electrical installation personnel according to the current national regulations Main circuit require...

Page 12: ...ion The standard configuration of the air pipe connection is 8 6mm hose joint When connecting air pipe the controller shall be at the OFF state and the air pipe shall be in the suspension non pressure...

Page 13: ...current 8 9 A Pre set 5 1 phase Rat voltage 200 240 Vac 6 Max 1 phase Rat input voltage 264 Vac 7 1 phase Rat power 2 2 KW 8 1 phase Rat current 12 A Pre set 9 Working temperature 20 60 10 Housing tr...

Reviews: