RS80-0200-1 Rev d (10-2010)
DCN0533
3.2 Density - Setpoint Adjustment - High (RS80 only)
The default density setting of the RS80 is High. This means that the switch is set to detect fluids with a specific grav-
ity of 0.8 and above. The Resonator can be configured to change the default settings externally with a magnet or
internally with the pushbuttons inside the enclosure.
To configure the Resonator with a magnet:
1. When the fork is “DRY” or “WET,” place a magnet at X position between 1-6 seconds (Figure 1). After this action
is performed, both LED1 & LED2 will briefly turn off.
2. Move the magnet to S2. After this action is performed LED 2 will turn green. This will set the High S.G. Setpoint
(Figure 2).
To configure the Resonator with pushbuttons:
1. When the fork is “DRY” or “WET,” depress buttons S1 & S2 simultaneously for 1-6 seconds (Figure 3). After this
action is performed, both LED1 & LED2 will briefly turn off.
2. Depress pushbutton S2. After this action is performed LED 2 will turn green. This will set the High S.G. Setpoint
(Figure 4).
Table 1 - For Specific Gravity > 0.8 (High)
OPERATION
LED 1
LED 2
NORMAL
GREEN OR RED
OFF
X for 1 - 6 Seconds
OFF
OFF
S2
OFF
GREEN
GREEN or RED
OFF
Figure 1
Figure 2
Figure 3
Figure 4
The chart below shows the set-up functions (operation column) and corresponding LED actions (LED 1 & LED 2 col-
umns).