22
Setup
Connecting alarm input/output terminal
䡵
Alarm input terminal
Connect infrared sensor, door sensor, metal sensor or sensor of manual
switch and the like.
●
To prevent noise from entering the internal circuit, supply non-voltage
setting signal.
●
Do not supply voltage.
●
Can be set via menu whether to set to alarm when the contact is short
(MAKE), or when the contact is open (BREAK). (
A
Pg. 37)
●
Supply such that the alarm signal continues for more than 200 ms. The
recognition of alarm signal may not be guaranteed if less than 200 ms.
䡵
Alarm output terminal
Connect to alarm devices such as alarm, indicator, light or buzzer.
●
As it is an open type collector output insulated by photocoupler, it will turn
on during alarm.
●
This terminal has polarity. Make sure to connect such as the voltage of +
terminal is higher than - terminal. It will be damaged if reverse voltage is
supplied.