10
www.juwent.com.pl
LIST OF COMPONENTS:
PZ,PW - control button: FT22; 380V/1.6A
L- LED
Rd - thermal safety device
M - motor
S1,S2,S3,SW - heating element contactors
PP - power mode selector
G1,G2,G3 - heating elements: 1000W,2000W/230V
Fig. 5 Wiring diagram AGE 4-12, AGE 5-18, AGE 6-27
9. AUTOMATICS
The heating unit is fitted with a THERMOSTAT of the heater element limiting and monitoring outlet
air temperature in case of air flow disturbances (e.g. fan failure). Thermostat temperature setting
range is 0
O
C to 100
O
C with constant hysteresis of 3
O
C. Monitoring temperature is factory set at 80
O
C,
and limit temperature is always higher by 20ºC than the preset temperature.Jako dodatkowa opcja,
aparaty mogą być wyposażone w następujące elementy automatyki:
L
PW
M
L
N
PE
RD
G1
G2
S1
S2
G3
S3
SW
SW
S1
S2
S3
SW
PZ
0 1 2 3
PP
SW