2.  Low  Voltage  Indicator,  red,  bright  indicate  the  voltage  of  the  battery  is  low.  Load 

could  not  normal working.  This  is  normal  phenomenon.  When  the  battery  voltage 

recover to 12.6V or (25.2v), the Load will be automatically working, at this time the 

indicator is off. 

3.  Charge Indicator, green, bright indicate the battery need to charge, flickering means 

float charging, off means charge has stop. 

 

RESET  Button: 

The  rated  output  current  of  this  MPPT  solar  charge  controller  is  20A

30A

,  if  there  is  short  circuit  or  overload  happened,  the  MPPT  controller  will  close 

output. ( Load indicator off, Low voltage indicator off.) 

If you need the MPPT controller recover work, please check the reasons and clear out the 

fault firstly. Then put a small stick such as toothpick, ball-pen tip inside the RESET hole, 

and press RESET button will be OK. 

Attention: 

1.  Please check the rated voltage of the solar panel, battery, load are all the same 

with 12V or 24V or 48V. 

2.  Please  pay  attention  to  connection,  do  not  connect  the  “+”  “-”  poles  of  solar 

panels and load wrong.( Wrong connection will be burn your MPPT controller) 

3.  Battery must be connected earlier than solar panels and load. When take off the 

system, Solar Panels must be take down first, then cut off battery. 

4.  The rated current of solar panel and load must be less than MPPT controller’s 

rated current. 

 