Securing the appliance to the
cabinet
A
B
Electrical installation
The manufacturer is not
responsible if you do not follow
the safety precautions from the
Safety chapters.
This appliance is supplied without a main
plug and a main cable.
Cable
Cable types applicable for installation or
replacement:
H07 RN-F, H05 RN-F, H05 RRF, H05 VV-F,
H05 V2V2-F (T90), H05 BB-F
For the section of the cable refer to the total
power on the rating plate. You can also
refer to the table:
Total power (W)
Section of the ca-
ble (mm²)
maximum 10380
3 phases: 5 x 2.5
2 phases: 4 x 4.0
1 phase: 3 x 6.0
Connecting the terminal board
The appliance has a six-pole terminal
board. The jumpers (bridges) are set for
operation on a 400 V three-phase with a
neutral wire.
1 = 45 mm
2 = 45 mm
3 = 60 mm
4 = 60 mm
= 70 mm
1
2
3
4
5
L 1 – 2 – 3 = phase cables
N 4 = neutral cable
= earth cable
If the mains voltage is different, rearrange
the jumpers on the terminal board (refer to
the connection diagram below). Connect
the ground cable to the terminal. After you
connect the supply cable to the terminal
board, attach it with a junction clamp.