Table 13: Clearance Requirements for the SRX550 Services Gateway
Requirement for Clearance
Recommended
Clearance
Location
Space for service personnel to remove and
install hardware components
8.7 in. (22 cm)
Front of the chassis
Space for service personnel to remove and
install hardware components
17.4 in. (44.2 cm)
Rear of the chassis
Space for cable management and organization
2.5 in. (6.35 cm)
Between front-mounting flange and
rack or cabinet edge
Space for the cooling system to function
properly and to maintain unrestricted airflow
around the chassis
6.0 in. (15.24 cm)
Between both sides of the chassis and
any non-heat-producing surface such
as a wall or cabinet side
RELATED DOCUMENTATION
SRX550 Services Gateway Description | 2
SRX550 Services Gateway Cabinet Size and Clearance Requirements | 47
Site Preparation Checklist for the SRX550 Services Gateway | 33
SRX550 Services Gateway Rack Size and Strength Requirements | 43
General Site Installation Guidelines for the SRX550 Services Gateway | 35
46
Summary of Contents for SRX550
Page 1: ...SRX550 Services Gateway Hardware Guide Published 2020 12 16...
Page 55: ...39...
Page 178: ...162...
Page 182: ...Restricted Access Warning 166...
Page 196: ...Jewelry Removal Warning 180...
Page 199: ...Operating Temperature Warning 183...
Page 206: ...190...
Page 210: ...194...
Page 213: ...197...