CAUTION:
Always keep the air filter in place while the services gateway is
operating. Because the fans are very powerful, they could pull small bits of wire
or other materials into the services gateway through the unfiltered air intake. This
could damage the services gateway components.
•
The shelf life of polyurethane filter varies from two years to five years depending on the storage
conditions. Store in a cool, dry, and dark environment. Wrap the media in plastic and store in an
environment with relative humidity between 40%- 80% and temperature between 40°F (4° C) to 90°F
(32° C). Note that if the material flakes, or becomes brittle when rubbed or deformed, it is no longer
usable.
Replacing the SRX5800 Services Gateway Air Filter
You should change the air filter every six months. To replace the air filter, perform the following procedures
in sequence:
1.
Removing the SRX5800 Services Gateway Air Filter | 274
2.
Installing the SRX5800 Services Gateway Air Filter | 275
Removing the SRX5800 Services Gateway Air Filter
CAUTION:
Do not run the services gateway for more than two minutes without the
air filter in place.
CAUTION:
Always keep the air filter in place while the services gateway is operating,
except during replacement. Because the fans are very powerful, they could pull small
bits of wire or other materials into the services gateway through the unfiltered air
intake. This could damage the services gateway components.
Before you begin to remove the air filter:
•
Ensure you understand how to prevent electrostatic discharge (ESD) damage. See
Electrostatic Discharge Damage” on page 505
.
Ensure that you have the following available:
274
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...