1. Calculate the power requirements (usage) as shown in
and
.
Table 42: Sample Power Requirements for an SRX5800 Services Gateway with SCB1 and RE1
Zone 1 Power
Zone 0 Power
Power
Requirement
Part Number
Chassis
Component
25 W
25 W
50 W
SRX5800BASE-HC-AC
Base system
320 W
320 W
320 W * 2 = 640 W
SRX5800-HC-FAN
High-capacity cooling
system
2925 W
585W * 5 = 2925 W
SPC2
See note below.
SPC - slots 0 through
4
570 W
570 W
IOC2 with two MICs
MPC - slot 5
240 W
150 W
90 W
SCB1 with
RE1
SCB 0 - slot 6
150 W
150 W
SCB1
SCB 1- slot 7
570 W
570 W
IOC2 with two MICs
MPC - slot 8
2925 W
585W * 5 = 2925 W
SPC2
See note below.
SPC - slots 9 through
13
Zone 1 total: 4080 W
Zone 0 total: 3990 W
SRX5800
standard-capacity AC
(not zoned) 8070 W
Total power requirement
183
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...