NOTE: To connect the DC source to an ACX7024 router, use a 12 AWG and 75°C temperature-rated or 14
AWG and 90°C temperature-rated stranded copper wire. To connect the DC power source to an ACX7024
in a data center or a central office, use a 14 AWG DC wire.

a. Secure the ring lug of the positive (+) DC power source cable to the RTN (return) terminal on the DC power

supply module using one of the terminal screws.

b. Secure the ring lug of the negative (–) DC power source cable to the –48V (input) terminal on the DC power

supply module using the other terminal screw.

c. Tighten the screws on the power supply module terminals until snug using the Phillips number 2 screwdriver.

Do not overtighten—apply 1.2 N-m of torque to the screws.

NOTE: After the input DC wires are crimped to the wiring lugs, cover the lugs and crimped area with a
suitable heat shrink sleeve to avoid exposed bare lug or crimped areas.

11. Replace the terminal block cover. Apply 0.5 N-m of torque to the screws.

12. Close the input circuit breaker.

NOTE: The switch powers on as soon as you connect it to power.

Step 2: Up and Running

IN THIS SECTION

Customize the Basic Configuration  |  7

6

Summary of Contents for Day One+ ACX7024

Page 1: ...the ACX7024 2 Power On 4 In this guide we provide a simple three step path to quickly get you up and running with your new Juniper Networks ACX7024 Cloud Metro Router We ve simplified and shortened th...

Page 2: ...ies that include support for the latest protocol and traffic engineering technologies enhanced security and precision timing for mobile backhaul applications Install the ACX7024 IN THIS SECTION What E...

Page 3: ...Here s how to install the ACX7024 in a two post rack 1 Wrap and fasten one end of the ESD grounding strap around your bare wrist and connect the other end of the strap to a site ESD point 2 Position t...

Page 4: ...dant feed input For source redundancy you ll need to install two DC power supplies in the ACX7024 Connect source A to one power supply module and source B to the second power supply module This config...

Page 5: ...negative You install this cable on the V input DC power input terminal CAUTION You must ensure that power connections maintain the proper polarity The power source cables might be labeled and to indic...

Page 6: ...he 48V input terminal on the DC power supply module using the other terminal screw c Tighten the screws on the power supply module terminals until snug using the Phillips number 2 screwdriver Do not o...

Page 7: ...SSH and make additional configuration changes You can always revert to the factory default configuration whenever you want Have the following information ready before you begin customizing the router...

Page 8: ...the chassis auto upgrade process edit root re0 delete chassis auto image upgrade 7 Stop zero touch provisioning ZTP edit root re0 delete system commit factory settings NOTE ZTP is enabled on the ACX70...

Page 9: ...run zkid 13237 id 512 614206 ztp py 31898 rm cannot remove var run zkid 13237 id No such file or directory 10 Optional Give the router a name If the name includes spaces enclose the name in quotation...

Page 10: ...em services ssh 16 To allow users to log in to the router as root through SSH include the root login statement edit system services ssh root re0 root login allow NOTE By default users are not allowed...

Page 11: ...nd Upgrade Guide Activate and manage your software licenses to unlock additional features for your ACX7024 router See Activate Junos OS Licenses Configure monitor and troubleshoot various interfaces o...

Page 12: ...your Juniper Networks devices Check out our free Web based training videos at Hardware Installation and Configuration Videos View a list of the many free technical trainings we offer at Juniper Visit...

Reviews: