background image

Presence detector universal 

Light Management  

Presence detector universal 

Art. No. PMU 360 WW

Presence detector universal 

Art. No. PMU 360 AL

Operating instructions 

1 Safety instructions 

Electrical equipment may only be installed and fitted by electrically skilled persons. 

Failure to observe the instructions may cause damage to the device and result in fire and 
other hazards. 

Danger of electric shock. Device is not suitable for disconnection from supply voltage. 
The load is not electrically isolated from the mains even when the device is switched off. 

Danger of electric shock. Always disconnect before carrying out work on the devise or 
load. At the same time, take into account all circuit breakers that supply dangerous 
voltage to the device or load. 

Do not press on the sensor window. Device can be damaged. 

The device is not suitable for use as a burglar alarm or other alarm. 

These instructions are an integral part of the product, and must remain with the end 
customer. 

2 Device components 

Figure 1: Device components 

(1)  Brightness sensor 
(2)  Sensor window 
(3)  Decor ring 
(4)  Up insert 
(5)  LED 
(6)  Adjuster 

time

, run-on time 

(7)  Adjuster 

lux

, Brightness 

1/8 

82542823 
J:0082542823 

18.09.2012 

Summary of Contents for PMU 360 WW

Page 1: ...lly isolated from the mains even when the device is switched off Danger of electric shock Always disconnect before carrying out work on the devise or load At the same time take into account all circuit breakers that supply dangerous voltage to the device or load Do not press on the sensor window Device can be damaged The device is not suitable for use as a burglar alarm or other alarm These instru...

Page 2: ...set The light is switched off in combination with dimmer inserts If no more movement is detected in the detection area and the run on time has elapsed This is done by first dimming the light to minimum brightness and switching it off after 5 minutes If the light has been dimmed to minimum brightness and the brightness exceeds 1 5 times the set value for longer than 10 minutes If the light was swit...

Page 3: ...the 2 wire extension or the the installation button Switching off the brightness evaluation The brightness evaluation can be switched off if the brightness is perceived as too dark after the light is switched off A 2 wire extension or an installation button is connected The presence detector has switched the light off due to adequate extraneous light e g daylight o Press the installation button wi...

Page 4: ...environment Selecting the installation location Figure 2 The presence detector is installed on the ceiling and monitors the surface under it figure 2 The presence detector has a detection area of 360 Die PIR sensor system operates with 6 detection levels and 80 lenses Figure 3 Detection field The range is approx 5 m in diameter at table height e g approx 80 cm At floor level the range diameter is ...

Page 5: ...ttered light o Connect flush mounted insert properly and mount in accordance with the desired orientation of the presence detector see instructions for flush mounted insert o Fit presence detector cover on flush mounted insert 5 2 Commissioning Testing the detection area The presence detector is mounted and connected properly o Pull off decor ring 3 o Set lux adjuster to3 figure 1 The presence det...

Page 6: ... set to the current brightness i If lux adjuster is on 0 the presence detector only switches on through operation of an extension In this case the switch off brightness is 400 lux o Attach decor ring 3 Calibrating the brightness value in combination with switch insert Brightness calibration is necessary to prevent light oscillations from occurring A light oscillation occurs when the presence detec...

Page 7: ...is on 0 the presence detector only switches on through operation of an extension In this case the switch off brightness is 400 lux o Attach decor ring 3 Setting the run on time The fewer the motions expected in the monitored area the longer the run on time setting should be This reduces the probability that the presence detector will switch off even though people are present Use 10 minutes as the ...

Page 8: ...ector see Connecting presence detectors in parallel Run on time too short Motion of persons is not detected Extend run on time using time adjuster see Setting the run on time Presence detector switches on and of constantly time adjuster is set to test Set run on time using time adjuster see Setting the run on time Presence detector switches off briefly and then on again immediately Brightness drop...

Reviews: