background image

 

KNX 

4-channel analog input module 

 

Ref.-no.: 2214 REG AM 

 

3. Installation 

The device is snap-fastened on a 35 x 7.5 mm rail as per EN 50022. 

An analog input module must be connected to the KNX/EIB device 
by means of the 6-pole system connector only (supplied with the 
analog input module). 

For operation, the 4-channel analog input module needs an external 24 V 
power source Art. no. WSSV10. 

4.  Power supply of connected sensors 

  The connected sensors can be supplied from ter U

 

and 

GND (see fig. 

c

). These terminals are provided in duplicate and  

internally interconnected. 

  The total current consumption of all sensors supplied this way must 

not exceed 100 mA. 

  In the event of overload or short-circuit bU

and GND, the 

power will be switched off. After removal of the fault, the power is 
switched on again automatically. 

  Sensors connected can also be supplied externally (e. g. if their 

current consumption exceeds 100 mA). In such case, they must be 
connected between terminals K1... K4 and GND. 

Attention! 
U

s

 

and GND must not be interconnected with the corresponding  

terminals of another device. 
Connected sensors must not be supplied with power from the  
connected KNX/EIB device (Risk of irreparable damage!). 

5. Connection 

 

Anschlussbild 

 

Summary of Contents for KNX 2214 REG AM

Page 1: ...rresponding terminals of another device Connected sensors must not be supplied with power from the connected KNX EIB device Risk of irreparable damage 2 Function This analog input module extends a KNX EIB weather station Art no 2224 REG W or a KNX EIB analog input Art no 2114 REG A by four additional sensor inputs for analog transducers Measuring data evaluation and limit processing take place in ...

Page 2: ...e provided in duplicate and internally interconnected The total current consumption of all sensors supplied this way must not exceed 100 mA In the event of overload or short circuit between US and GND the power will be switched off After removal of the fault the power is switched on again automatically Sensors connected can also be supplied externally e g if their current consumption exceeds 100 m...

Page 3: ...les without adapting their project configuration and subsequent downloading into the KNX EIB device is not allowed as this will result in system failure 7 Status LED During commissioning of the module On Module ready for operation self test OK Quickly blinking Module initialization in progress Slowly blinking Module not configured in KNX EIB device Off Module initialized and in operation Precondit...

Page 4: ...C Storage transport temp 25 C 70 C Humidity Ambient storage transport 93 r h max no condensation Protective system IP 20 as per EN 60529 Installation width 4 modules 72 mm Weight approx 150 g Connections Inputs power supply screw terminals single wire 0 5 mm to 4 mm stranded wire without ferrule 0 34 mm to 4 mm stranded wire with ferrule 0 14 mm to 2 5 mm Connection to KNX EIB device 6 pole system...

Page 5: ...T JUNG GMBH CO KG Service Center Kupferstr 17 19 D 44532 Lünen Service Line 49 0 23 55 80 65 51 Telefax 49 0 23 55 80 61 89 E Mail mail vki jung de Technik allgemein Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 E Mail mail vkm jung de Technik KNX EIB Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 E Mail mail vkm jung de The Sign is a free trade sign addressed exclusiv...

Reviews: