Art.-No.: 2095 LUX
Function:
Manual operation
Object
h
2
Function
Switching
Name
Automatic OFF via
Type
1-bit
DPT
1.001
Flag
C, W, -, -
Description
Enter here the group address via which the lighting will be switched manually
if required. When a switching command is received via this object, the
brightness control or constant light regulation is deactivated. The telegram
contents (0 or 1) are not relevant here. The lighting setting is then not changed
by the controller until the automatic mode is switched on again via Object 1.
Function:
Manual operation
Object
h
3
Function
Dimming
Name
Automatic OFF via
Type
4-bit
DPT
3.007
Flag
C, W, -, -
Description
Enter here the group address via which the lighting will be dimmed manually if
required. When a dimming command is received via this object, the brightness
control or constant light regulation is deactivated. The telegram contents
(brighter or darker) are not relevant here. The lighting setting is then not
changed by the controller until the automatic mode is switched on again via
Object 1.
Function:
Manual operation
Object
h
4
Function
Dimming value
Name
Automatic OFF via
Type
1-byte
DPT
5.001
Flag
C, W, -, -
Description
Enter here the group address via which the lighting will be dimmed manually
to a dimming value if required. When a dimming value command is received
via this object, the brightness control or constant light regulation is
deactivated. The telegram contents (dimming value in %) are not relevant
here. The lighting setting is then not changed by the controller until the
automatic mode is switched on again via Object 1.
Note: Under no circumstances may the group address used in Object 10
(dimming value of the controller to the lighting in case of constant light
regulation) be used here, because otherwise it would disable itself when the
first dimming value is transmitted!
Function:
External setpoint specification - constant light regulation
Object
h
5
Function
Value in lux
Name
Constant light
regulation setpoint
Type
2-byte
DPT
9.004
Flag
C, W, -, R
Description
This object is only available if the parameter "Operating mode" is set to
"Constant light regulation" and the parameter "Setpoint as" is set to
"Communication object". Then if necessary the brightness setpoint which is
set at the factory to 600 lux can be overwritten using this object. If a new
setpoint is received, it is immediately saved in the non-volatile memory of the
device and used for control.
Page 14 of 27
Software "Brightness controller A01001"
Object table