Deleting all radio transmitters
Load is switched off.
o
Press the programming button for approx. 20 seconds.
After approx. 4 seconds the LED blinks.
After approx. 20 seconds the LED flashes.
o
During the next 6 seconds, release the programming button and press it again for approx.
1 second.
LED lights up. The radio transmitters will be deleted.
LED blinks quickly. All radio transmitters have been deleted.
6 Appendix
6.1 Technical data
Rated voltage
AC 230 V ~
Mains frequency
50 / 60 Hz
Control voltage
1 V ... 10 V
Control current
max. 15 mA
Ambient temperature
0 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
Connected load
Ohmic load
1800 W
Electronic ballast
Type-dependent
Tronic transformer
Type-dependent
Contact type
µ contact
Circuit breaker
max. 10 A
Connection
Single stranded
1.5 ... 4 mm²
finely stranded without conductor sleeve
0.75 ... 4 mm²
finely stranded with conductor sleeve
0.5 ... 2.5 mm²
Fitting width
72 mm / 4 modules
Teachable radio transmitter
max. 30
6.2 Troubleshooting
Device does not respond, or only sometimes.
Cause 1: battery in the transmitter is empty.
Change the battery.
Cause 2: Radio range exceeded. Structural obstacles reduce the range.
Check the installation situation.
Using a radio repeater.
6.3 Accessories
Master receiver for rail mounting
Art.-No.: FK 100 REG
4/5
32550213
J:0082550213
29.07.2010
Radio Management
Radio push-button controller for rail mounting