eNet radio DALI gateway 1-gang mini
–
DALI supply for a maximum of 12 subscribers
–
Parallel switching of up to 6 DALI control units with the option of supplying up to 72 DALI
subscribers
–
Switch-on brightness can be saved permanently
–
Minimum brightness can be saved permanently
–
Scene operation possible
–
Status indication with LED
–
Status feedback to radio transmitter
–
DALI ballast is switchable with Prog button
Can be set with eNet server:
–
Maximum brightness
–
Dimming speed
–
Switch-on delay / switch-off delay
–
Dim up/dim down ramp
–
Switch-off warning
–
Operation locks
–
Continuous on, Continuous off
–
Hotel function
–
Run-on time
–
Light control
When operating with the eNet Server, operation and signalling could vary from what is de-
scribed here.
Supplementary functions with eNet Server:
–
Fully encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
–
Update of the device software
–
Repeater function
–
Reading of error memory
Behaviour after mains voltage failure and return
The response after mains voltage return can be configured with the eNet server. Default setting:
The light is switched off after mains voltage return. After a brief voltage failure or in the case of
operation on several conductors, it might take a few seconds until the light is switched off.
Within this time frame, a value stored in the DALI ballast – PowerON-Level – is retrieved.
The brightness of the lighting when DALI- telegrams are missing – PowerON-Level – and
in case of DALI system voltage failure – SystemFailure-Level – is stored in the DALI bal-
last and cannot be changed using the actuator.
4
Operation
Operation with radio transmitter
Operation is with radio transmitters, please observe the radio transmitter instructions.
Operation always applies to all the connected DALI ballasts, broadcast.