background image

The range of the system can be optimised by selecting the optimal installation location, taking
into account the structural circumstances.

Figure 2: Reduced range due to structural obstacles

Example of penetration of various materials:

Material

Penetration

Wood, Plaster, Plasterboard

approx. 90%

Brick, Chipboard

approx. 70%

Reinforced concrete

approx. 30%

Metal, Metal grid

approx. 10%

Rain, Snow

approx. 1-40%

Intended use

-

Reception of radio telegrams and conversion into wire-bound data

-

Activation of RMD radio actuators, e.g. switch actuators, dim actuators or shutter actuators

-

Installation in distribution boxes on DIN rail according to DIN EN 60715

Product characteristics

-

Up to 30 RMD radio actuators can be connected

-

Integrated antenna 

-

External antenna can additionally be connected in case of disadvantageous installation
conditions, e.g. metallic distribution boxes

4 Information for qualified electricians

4.1 Fitting and electrical connection

DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.

Connecting and mounting the device

Maintain a distance of at least 1 m between transmitter and receiver in order to prevent
overmodulation of the receiver.

2/4

32549823
J0032549823

24.10.2016

Radio Management 

Master receiver for rail mounting

Reviews: