background image

Standard push-button module with integrated BCU 

Standard push-button module with integrated BCU, 1-gang 

Art.-No.: 4071 TSM

Standard push-button module with integrated BCU, 2-gang 

Art.-No.: 4072 TSM

Standard push-button module with BCU, 3-gang 

Art.-No.: 4073 TSM

Standard push-button module with integrated BCU, 4-gang 

Art.-No.: 4074 TSM

Operationsmanual 

1 Safety instructions 

Electrical equipment may only be installed and fitted by electrically skilled persons. 

Failure to observe the instructions may cause damage to the device and result in fire and 
other hazards. 

Use only the enclosed plastic screws for fastening to the supporting frame. Otherwise 
safe operation cannot be ensured. Electrostatic discharges can cause defects in the 
device. 

These instructions are an integral part of the product, and must remain with the end 
customer. 

2 Function 

System information 

This device is a product of the KNX system and complies with the KNX directives. Detailed 
technical knowledge obtained in KNX training courses is a prerequisite to proper 
understanding.  
The function of this device depends upon the software. Detailed information on loadable 
software and attainable functionality as well as the software itself can be obtained from the 
manufacturer´s product database. Planning, installation and commissioning of the device are 
carried out with the aid of KNX-certified software. The latest versions of product database and 
the technical descriptions are available on our website. 

Intended use 

Operation of loads, e.g. light on/off, dimming, blinds up/down, brightness values, 
temperatures, calling up and saving light scenes, etc. 

Installation in appliance box to DIN 49073 

Product characteristics 

The pushbutton functions switching, dimming, controlling blinds, valuators, calling up 
moods, etc., depending on the application selected 

Completion with keyset  

One red status LED per button 

A blue operation LED as an orientation light and to indicate the programming status  

Integrated bus coupling unit 

3 Operation 

Operating a function or load 

Each button is divided into two halves, with a function assigned to each of them. Operation 
depends on the specific function.  

Switch: Short press on the button. 

Dim: Long press on the button. The dimming process ends when the button is released. 

Move Venetian blind: Long press on the button.  

Stop or adjust Venetian blind: Short press on the button. 

Call up light scene: Long press on the button. 

Save light scene: Long press on button. 

1/5 

32566613 
J:0082566613 

24.11.2009 

Summary of Contents for 4071 TSM

Page 1: ...ainable functionality as well as the software itself can be obtained from the manufacturer s product database Planning installation and commissioning of the device are carried out with the aid of KNX certified software The latest versions of product database and the technical descriptions are available on our website Intended use Operation of loads e g light on off dimming blinds up down brightnes...

Page 2: ...t Snapping on the adapter frame o With the adapter frame 3 in the correct orientation snap it from the front onto the pushbutton module 4 picture 1 Note marking TOP Fitting and connecting the device picture 1 Mounting the push button module 1 Supporting frame 2 Design frame 3 Adapter frame 4 Push button module 5 Fastening screws 6 Buttons 7 KNX connection terminal 8 Box screws Supporting frame sid...

Page 3: ...e mounting the buttons 6 load the physical address into the device see chapter 4 2 Commissioning 4 2 Commissioning Loading the physical address and application software Configuration and commissioning with ETS3 0d Patch A or more recent The device is connected and ready for operation The buttons are not mounted yet i If the device does not receive any application software or the wrong application ...

Page 4: ...ent 5 Appendix 5 1 Technical data KNX medium TP 1 Commissioning mode S mode Rated voltage KNX DC 21 V 32 V SELV KNX power consumption typical 150 mW Connection mode KNX Connection terminal Safety class III Ambient temperature 5 45 C Storage transport temperature 25 70 C 5 2 Accessories Cover kit 1 gang complete Art No 401 TSA Cover kit 2 gang complete Art No 402 TSA Cover kit 3 gang complete Art N...

Page 5: ...5 80 61 89 mail vka jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 mail vkm jung de KNX equipment Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 mail vkm jung de The Œ symbol is a free trade symbol which is solely intended for the authorities and does not guarantee any properties ALBRECHT JUNG GMBH CO KG Volmestraße 1 D 58579 Schalksmühle Telef...

Reviews: