KNX/EIB
product documentation
Page: 10 of 15
Hardware description
Application:
4.
Shutter 102C01
Executable from mask version:
1.0
Number of addresses (max):
12
dynamic table handling:
Yes
:
No
Number of assignments (max):
12
maximum length of table:
24
Communication objects:
8
Object
Function
Name
Type
Flag
0 Short-time operation
Rocker 1
1 bit
C, W, T
1 Short-time operation
Rocker 2
1 bit
C, W, T
2 Short-time operation
Rocker 3
1 bit
C, W, T
3 Short-time operation
Rocker 4
1 bit
C, W, T
4 Long-time operation
Rocker 1
1 bit
C, W, T
5 Long-time operation
Rocker 2
1 bit
C, W, T
6 Long-time operation
Rocker 3
1 bit
C, W, T
7 Long-time operation
Rocker 4
1 bit
C, W, T
Object description
Objects:
0 – 3
Short-time operation:
1-bit object for short-time operation of a shutter
4 – 7
Long-time operation
1-bit object for long-time operation of a shutter
Important:
Unused communication objects must be projected with dummy group addresses. Otherwise risk of
malfunctions.
Scope of functions
•
Function of operation LED parameterizable
•
Time between two telegrams (time between STEP and MOVE) presettable