17
2 Description
2.1
Brief description
The JUMO LOGOSCREEN 600 paperless recorder features a resistive touchscreen and an in-
tuitive, icon-based operation and visualization concept that makes it very easy to use.
There are different versions of the JUMO LOGOSCREEN 600 available for process data re-
cording. These range from the device version without measuring input in which up to 24 pro-
cess values are read (master) or received (slave) from external systems via Modbus, through
to a device version with six measuring inputs (universal analog inputs), two analog outputs, 12
digital inputs, and 12 individually switchable digital inputs/outputs. In the version with FDA-com-
pliant data recording all the requirements are met in accordance with 21 CFR Part 11.
The JUMO LOGOSCREEN 600 can display data using the default visualizations, such as
curve diagram (vertical or horizontal), bar graph, text image (numerical), or digital diagram. For
batch-related processes a special batch recording is available which allows the storage of ad-
ditional information. In addition, users can create up to six individual process screens with up
to 100 objects per process screen to fit their requirements using the setup program.
In addition to the setup program further powerful PC programs are available, e.g. for the eval-
uation of archived data and for the administration of access control.
2.2
Block diagram
Setup programm
PCC, PCA3000
PCS, PCAT
Software
Internal channels
6 math channels (optional)
6 logic channels (optional)
6 counters/integrators
1 high-speed counter
Inputs/outputs
Option 1, option 2:
3 analog inputs,
6 digital inputs,
1 analog output
each
12 digital inputs/outputs,
incl. 1 high-speed counting input
(up to 12.5 kHz)
Option 3:
Display/operation
JUMO LOGOSCREEN 600
Voltage supply
Display
Operation
14,5 cm (5,7”) TFT color screen
640 x 480 pixel,
65536 colors
Touchscreen (resistive)
As standard:
24 external analog inputs and
24
14
texts (10 batch texts,
4 event texts)
external digital inputs and
external
Inputs via interface
As standard:
1 relay (changeover contact)
Relay output
AC 110 to 240 V +10/-15 %,
48 to 63 Hz
AC/DC 20 to 30 V, 48 to 63 Hz
Interfaces
As standard
1x Ethernet 10/100 MBit/s
1x USB host (flash drive)
1x USB device (setup)
barcode scanner)
:
1x RS232/RS485
(Modbus master/slave or
Internal memory:
1 GByte
(data transfer via interface
or USB flash drive)
Measurem.-data memory